II.2.

 

Space required for maintenance 

Generally speaking, it is desirable to provide access space of at least the width of the unit on the access side for maintenance.  
More specifically for the Pyrostar range, an extra 200 mm free space is needed on the opposite side to service side. 
 

II.3.

 

II.3 Installation 

 
The unit must be laid on a sufficiently rigid and flat surface (use vibration mounts if necessary).  
Install the unit such that bad weather or ambient temperature cannot damage the internal items of the unit during installation as well as when 
used later (possibly provide a protective cap). 
F400-120 fans should be installed outdoor or, when installed indoor, separated from other volumes by a 1 hour fire-resistant wall. The door of the 
technical room should be ½ hour fire resistant. Ventilation of this technical room should comply with the installed materials. 
F400-120 fans should be wired to a converter only in Comfort mode and run at full speed when extracting smoke. 
 
If the motor is equipped with overheat protection, they should be wired to the converter so it can protect the motor during Comfort mode. 
  

 

 

III.

 

ELECTRICAL WIRING 

 

III.1.

 

Wiring 

Wiring should be done according to local laws and specific site recommandations.  
Depending on the boxfan

s construction, it should be done on the padlockable switch or on the optional control box factory mounted on the casing. 

 

 

III.2.

 

1 speed motors 

 

1 speed 

 2 voltages (star/ delta connexions) 230V/400V or 400/690V 

 2 and 4 poles motors 

Padlockable switch 

Fan star / delta connexion 

 

 

 
 
 
 

Summary of Contents for PYROSTAR F400-120

Page 1: ...PYROSTAR SMOKE FAN F400 120 MS MTG 001 Ind E 01 10 2019 Page 1 8 INSTALLATION AND COMMISSIONING MANUAL...

Page 2: ...I 1 Handling 3 II 2 Space required for maintenance 4 II 3 II 3 Installation 4 III ELECTRICAL WIRING 4 III 1 Wiring 4 III 2 1 speed motors 4 III 3 III 3 2 speeds motors 5 III 4 III 4 2 speeds motors se...

Page 3: ...handled using a fork lift truck ensure this supports the load bearing structure and does not touch the panels enclosing the unit If the device is moved using a crane use four cables of identical lengt...

Page 4: ...outdoor or when installed indoor separated from other volumes by a 1 hour fire resistant wall The door of the technical room should be hour fire resistant Ventilation of this technical room should com...

Page 5: ...4 III 4 2 speeds motors separate windings 2 speeds 1 voltage separate windings 400 V 4 6 poles motors Low speed High speed Once wiring is done check if the impeller is turning in the right direction I...

Page 6: ...eck pulleys alignment both motor and impeller pulleys along with belt tension IV 2 IV 2 Belt tension Please refer to the following table for belt s tension I pulleys axle spacing F belt deflection P f...

Page 7: ...rflow After settings make sure both locking screws are secured and the the pulleys alignment is fine V Troubleshooting Problem Main reasons How to solve Fan not running Main power off Thermal motor pr...

Page 8: ...PYROSTAR SMOKE FAN F400 120 MS MTG 001 Ind E 01 10 2019 Page 8 8 VI NOTES Date Observations...

Reviews: