IDROSTUFE
32
16.2 PROBLEM SOLVING (THERMOSTOVE)
PROBLEM
POSSIBLE CAUSES SOLUTIONS
INTERVENTION
In automatic
position, the boiler
always works at
maximum power
Thermostat set to
the minimum
Reset the thermostat temperature
Room thermostat
in a position that
always detects cold
Change the position of the thermostat
Faulty temperature
detection probe
Check and, if necessary, replace the probe
Defective or broken
control panel
Check and, if necessary, replace the panel
The boiler does not
start
Power outage
Make sure the power cable is plugged in and the main switch
is in the “I” position.
Blocked pellet
probe
Release it via the rear thermostat. If it happens again, call
customer service.
Broken fuse
Replace the fuse
Broken manostat
(block signal)
Low water pressure in the boiler
Clogged smoke
duct or exhaust
Clean the smoke exhaust and/or smoke duct
Water temperature
probe has tripped Call customer service
Summary of Contents for IDRO PRINCE3 12
Page 44: ...NOTE ...
Page 45: ...NOTE ...