  IM-BW4-5-02

[240013014 Rev. B [12/15/2020]

1. 

Check your local codes and utility requirements 

before installation. Installation must be in accordance 

with their directives, or follow 

NFPA 31 Standard for 

Installation of Oil Burning Equipment

, latest revision.

2. 

Before servicing, allow boiler to cool. Always shut off 

any electricity and oil to boiler when working on it. 

3. 

Inspect oil line and connections for leaks.

4. 

Be certain oil burner nozzle is the size required. Over-

firing will result in early failure of the boiler sections. 

This will cause dangerous operation.

5. 

Never vent this boiler into enclosed space. Always vent 

to outside. Never vent to another room or inside a 

building.

6. 

Be sure there is adequate air supply for complete 

combustion.

7. 

Follow regular service and maintenance schedule for 

efficient and safe operation.

8. 

Keep boiler area clean and free of combustible material, 

gasoline and other flammable vapors and liquids.

9. 

Oil burners are not do-it-yourself items. This boiler 

must be installed and serviced by qualified professionals 

using combustion test instruments.

 WARNING

Burn and scald hazard.  Safety relief valve could       

discharge steam or hot water during operation.       

Install discharge piping per these instructions.

!

     

10. 

Be aware when piping the safety relief valve if system 

pressure exceeds safe limit of 30 pounds per square 

inch, the safety relief valve will automatically lift 

open. Lifting of the safety relief valve can discharge 

large quantities of steam and hot water, which may 

damage the surroundings. Before installing the safety 

relief valve read the manufacturer’s instructions and 

maintenance section of the manual on safety relief 

valves.

11. 

Installation and sizing of the expansion tank must 

consider heating systems total water volume, 

temperature, boiler initial fill pressure, and system 

arrangement. Improperly installed and sized expansion 

tank may result in frequent lifting of the safety 

relief valve or other heating system problems. For 

proper installation, sizing, and maintenance of the 

expansion tank follow guidelines established by tank 

manufacturer.

12. 

Expansion tank performance and life expectancy can 

be hindered by overfilling the boiler. Recommend initial 

fill pressure of 10-12 psig. For higher fill pressures 

expansion tank’s air charge will need to be increased to 

match fill pressure. Consult manufacturer’s guidelines 

for sizing and selection.

13. 

Purging the heating system of air and gases when 

first putting boiler into service is critical for proper 

circulation and quiet performance. Once air and gases 

are purged, for boiler installations using float type 

vents, air vents should be closed for normal operation. 

If air is heard or noticed by loss of heat, purge system 

and open vents for short period of time.

SAFE INSTALLATION AND OPERATION

NOTICE

This boiler has been designed for residential 

installations. If used for commercial applications, 

all jurisdictional requirements must be met. This 

may require wiring and/or piping modifications. 

Manufacturer is not responsible for any changes to 

the original design.

 WARNING

Fire, explosion, burn, scald hazard.  Use only 

number 2 fuel oil. Do not use gasoline, kerosene, 

crankcase oil or any oil containing gasoline. Failure 

to follow these instructions could result in death or 

serious injury.

!

     

 WARNING

Combustion chamber insulation in this product 

contains ceramic fiber material. Ceramic fibers can 

be converted to cristobalite in very high temperature 

applications. The International Agency for Research 

on Cancer (IARC) has concluded, Crystalline silica 

inhaled in the form of quartz or cristobalite from 

occupational sources is carcinogenic to humans 

(Group1). Avoid breathing dust and contact 

with skin and eyes. Use NIOSH certified dust 

respirator (N95). This type of respirator is based 

on the OSHA requirements for cristobalite at the 

time this document was written. Other types of 

respirators may be needed depending on the job 

site conditions. Current NIOSH recommendations 

can be found on the NIOSH website 

 https://

www.cdc.gov/niosh/topics/silica/.

  approved 

respirators, manufacturers, and phone numbers are 

also listed on this website. Wear long-sleeved, loose 

fitting clothing, gloves, and eye protection. Apply 

enough water to the combustion chamber lining to 

prevent dust. Wash potentially contaminated clothes 

separately from other clothing. Rinse clothes washer 

thoroughly.

NIOSH stated First Aid. Eye: Irrigate immediately. 

Breathing: Fresh air.

!

  

Summary of Contents for BW4BAH000112

Page 1: ...AH000112 BW5BAH000112 BW5RAH000112 BW4BAH000175 BW4RAH000175 BW5BAH000175 BW5RAH000175 Models Series D BW4BAH000217 BW4RAH000217 BW5BAH000217 BW5RAH000217 CAC BDP 7310 WEST MORRIS ST INDIANAPOLIS IN 4...

Page 2: ...nts portion of remaining heat that can be applied to heat radiation or terminal units finned tube baseboard cast iron radiators radiant floor etc Difference between Heating Capacity and Net AHRI Ratin...

Page 3: ...B R AH000217ADAA 1 55 217 189 164 86 0 5 13 7 21 6 11 Mbh 1 000 BTU per hour BTU British Thermal Unit Heating Capacity based on 13 1 CO2 with a 0 02 w c draft over fire and a 1 smoke or less Testing w...

Page 4: ...ing needs can scald and cause permanent injury Children elderly and infirm or physically handicapped persons are more likely to be permanently injured by hot water Never leave them unattended in batht...

Page 5: ...mance and life expectancy can be hindered by overfilling the boiler Recommend initial fill pressure of 10 12 psig For higher fill pressures expansion tank s air charge will need to be increased to mat...

Page 6: ...replacement of any parts that may normally require attention Install boilers at least 6 from combustible material on left side rear and above and at least 24 on right side and front Allow at least 24...

Page 7: ...ION FROM RADIATION CIRCULATING PUMP IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED S...

Page 8: ...gs communicating directly with additional room s of sufficient volume so the combined volume of all spaces meets the criteria for unconfined space Total input of all combustion equipment installed in...

Page 9: ...all equipment in the enclosure 3 When communicating with outdoors through horizontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of...

Page 10: ...elbow provided with boiler See Figures 6a and 6b A Install safety relief valve with spindle in vertical position B Do not install shutoff valve between boiler and safety relief valve C Install dischar...

Page 11: ...o prevent this condensation in boiler and venting is 120 F Boiler used in heating system where design water temperatures below 140 F are desired e g radiant floor heating a 3 way or 4 way mixing valve...

Page 12: ...RRANGED FOR POWER PURGING AIR OUT OF THE SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 Figure 7 Bypass Piping Arrangement Diagram SYSTEM PIPING Adjust two thro...

Page 13: ...IPING PUMPS AWAY FROM EXPANSION TANK NOTE CIRCULATORCANALSOBEINSTALLED ON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM...

Page 14: ...ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure...

Page 15: ...E BOILER CIRCULATOR ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATO...

Page 16: ...t draws not continuous flow NOTICE Do not use tankless coil if your water is excessively hard with lime or other deposits which will accumulate inside the coil When using tankless coil boiler is confi...

Page 17: ...increase fuel consumption Tankless coil performance will fall as concentration of antifreeze is increased Refer to boiler and piping water volumes tables BOILER WATER VOLUMES Number of Boiler Section...

Page 18: ...d boilers for connections to vents or chimneys vent installations shall be in accordance with applicable provisions of NFPA 31 Standard for the Installation of Oil Burning Equipment latest edition and...

Page 19: ...T 1 4 INCH PER FOOT OF HORIZONTAL RUN MUST BE AT LEAST 4 INCHES THICK AND BE TIGHT TIGHT CLEAN OUT DOOR SEALED IN THIMBLE TIGHT SMOOTH CORRECTLY SIZED Minimum Height Must be 3 FT higher than highest p...

Page 20: ...comply with the latest revision of the National Electrical Code any other national state or local codes or regulations Connect 120 volt electrical supply to L1 and L2 terminals on limit and two therm...

Page 21: ...Control with Riello F5 Burner ELECTRICAL WIRING When low limit is used set ELL Parameter on L7248 Honeywell control to ON Boilers factory equipped with tankless coil are factory set to ON When low lim...

Page 22: ...lve When power purging drain valve runs air free close isolation valve or zone valve Repeat this procedure for remaining heating zones C Once all zones are filled with water and purged of air close po...

Page 23: ...a lack of combustion air burner flame will be dark orange and formation of soot will occur in heating unit In buildings of conventional frame brick or stone construction that do not have utility rooms...

Page 24: ...5 BAH000217 AFG50MDASN 1 55 2 1 2 1 25 60 B 155 NO V1 2 10 2 2 3 4 RIELLO 40F5 BOILER MODEL BURNER MODEL INPUT RATE gph INSERTION DEPTH DELAVAN OIL NOZZLE PUMP PRESSURE psi TURBULATOR SETTING AIR SHU...

Page 25: ...ero and four are scale indicators only From left to right first line is 4 and last line 0 On some models scale indicators are 0 and 3 Figure 15 Burner Adjustments and Settings Figure 16 Riello Electro...

Page 26: ...floor on inside wall Locate thermostat to sense average room temperature avoid the following THERMOSTAT LOCATIONS TO AVOID DEAD SPOTS HOT SPOTS COLD SPOTS Behind doors Concealed pipes Concealed pipes...

Page 27: ...boiler and tank Water will rise to normal height in tank if system has automatic fill valve otherwise manually refill system Diaphragm Expansion Tank Tank may become water logged Frequent automatic op...

Page 28: ...ly vacuum soot accumulations from combustion chamber area take care to not damage any of refractory or blanket insulation To gain access to combustion chamber first check that shut off valve on fuel o...

Page 29: ...5 Install burner drawer assembly make sure head location and size if applicable are per manufacturer s recommendations If burner being used has damaged head replace head with same head recommended fo...

Page 30: ...o instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It may be in closed position Circulating pump not running Check over current protection Check re...

Page 31: ...31 IM BW4 5 02 240013014 Rev B 12 15 2020 Taco 007 Pump Curve PUMP CURVE 007...

Page 32: ...l energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that r...

Reviews: