C-TEC BF562-1 Installation Instructions Download Page 1

FIRE ALARM

ancillaries

Approved Document No. DFU0056210 Rev 6

WARNING: THIS PSU MUST BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND TECHNICALLY COMPETENT 
PERSON. THIS PSU IS A PIECE OF CLASS 1 PERMANENTLY CONNECTED EQUIPMENT AND MUST BE RELIABLY EARTHED.

SW

1

0V

CONF

INPUT

CHG

INHB

CONF

OUT

FAUL

T REL

AY

NC

CO

M

NO

 CONN6

THIS 

WAY UP

 CONN5

+V

BA

TTE

RY

0V

+V

OUTPUT

0V

 CONN4

Battery

Fuse (F2)

F2

1

2

3

4

ON

1

2

3

4

ON

Exposed live parts under cable cover.
Isolate first before removing the small cable cover.
No user serviceable parts under cover.

HAZARDOUS VOLTAGES LED (Red Steady)

When lit red, hazardous voltages

are present under the cover

.

Mains Input 230 V, 50/60 Hz, 0.4 A

L = Live,   N = Neutral,        = Earth

Terminate mains cable to CONN1.

Incoming Mains Cable

This cable must be segregated from other cables and only

 enter the panel through the top right-hand drill outs.

(Must be externally fused to ≤ 6 amps)

CHG INHB (CONN6)

Connect to 0 V to 

inhibit battery charger.

CONF INPUT/OUT (CONN6)

Configurable Input/Output.

For OEM use. Do not connect.

PSU Earth Distribution Strap

DO NOT operate the PSU without first connecting 

this strap to the base earth distribution post.

THERM (PL3)

Battery Thermistor Connector.
Optional BF322 PSU Remote Battery Temp. Sensor 
available at c-tec.com.

N

L

CONN1

Table 1 - PSU Status LED (Amber)

DIP SWITCH

DIP S/W 1 = For OEM use.

OFF (DOWN) = Defaults.

DIP S/W

OFF (DOWN)

ON (UP) 

2

3

4

Battery Resistance

Threshold 1.5 Ohm

Battery Resistance 

#2

Threshold 6 Ohm

Battery Charge Rate 

#2

0.5 A (3.2 Ah to 7 Ah)

Battery Charge Rate

1 A (7 Ah to 17 Ah)

Battery Fitted

Battery Not Fitted 

#2

3 A MINI

®

automotive
blade fuse

Mains Fuse (F1)

T 1 A H 250 V, 20 mm ceramic,

T=Time Delay, H=High Breaking Capacity

PL3

See Table 4 - Technical Specification 

overleaf for further details

General Fault Relay (CONN4)

1 A @30 Vd.c.

COM

NC

NO

Relay Fault-Free State

Table 2 - DIP Switch Settings

Supply Output (CONN5)

24 Vd.c. nominal

Red Wire

Black Wire

0V

+V

Battery Connector (CONN5)

2 X 12 V, 17 AH

+

+

+

+

-

-

-

-

THERM

PL2

DISPL

AY

PL3

FLASHES

1
2
3

Mains Failure

Battery Voltage Low (≤23 V)
Battery Voltage Critical (≤22 V) 

Charger Failure

Battery Not Fitted selected (indicates DIP S/W 4 position)

Battery Resistance Fault (level set by DIP S/W 2 position)

Output Over Voltage (>30 V)

4
5

6

7

8

Not Used (previously used to indicate Charger Healthy)

LED STATUS   (LED Off = Normal)

Battery Charger Inhibited (Warning only - Not a fault)

Steady

Scan the QR Code to 
download your 
documentation or visit 
www.c-tec.com/info/psu-
resources.html)

The BF562-1 is a boxed mains input to regulated DC PSU, providing 1.5 A @ 24 Vd.c. nominal, designed for use with 

fire and security systems. Combining the functions of a PSU, battery charging unit and battery monitoring unit, it is 

fully compliant with EN 54-4 + A1 + A2 and has been built to comply electrically/environmentally with EN 50131-6 

(Type A, up to Grade 4 

#1

, Environmental Class II). The PSU is an approved product by BRE and VdS.

All wiring must be installed in accordance with all applicable national, regional or local standards. In the UK this is 

BS 7671 (IET Wiring Regulations). Fuses must comply with IEC/EN 60127-2. See Fig.1 for PSU connection details.

1 of 2

BF562-1 (24 V DC, 1.5 A) Installation Instructions

EN 54-4, EN 50131-6 Boxed Power Supply Unit (PSU)

Fig.1 - PSU Layout & Connections

Over Current / Over Load Protection:

 

If the output load attempts to pull current in excess of the PSU rating, the PSU 

will shut-down and attempt to auto-recover after approx. 10 seconds, and will continue to do so until the overload 

is removed. If the PSU is subjected to a short circuit across the output terminals, the PSU may trip and require power 

cycling to reset. Reset by switching off mains and disconnecting the batteries, then wait for the red ‘Hazardous Voltage 

Present’ LED to extinguish before re-applying mains and batteries. Check the battery fuse (F2) has not operated.

WARNING: There is a risk of explosion if an incorrect battery type or size is used. Always dispose of used 

batteries in accordance with the battery manufacturers instructions and local regulations. Batteries are heavy 

and can produce dangerously high currents if shorted. Take care when handling and routing battery leads to 

avoid damage. The batteries must be safely secured by the cable ties (supplied in the accessories).

2831

17

176p

Note: On a standard ‘as-supplied’ unit, DIP Switch 4 (‘Battery Not Fitted’) is OFF (DOWN) and a fault will occur on 

initial power-up if fully charged batteries are NOT connected. See Table 2 - DIP Switch Settings (Fig.1).

VdS

G218033

Read these instructions before installation and operation