41
Copyright© BYD Europe B.V. all rights reserved.
•
Following the diagram. (See Figure48)
The Module BMS J1 interface of the module in top of cabinet 1 does not need to be connected.
7.3.2
Power cables between Modules.
DANGER
•
Only a single person is allowed to manipulate the system in the same moment- but at
least 2 person in the room.
•
After connection cover the terminals to prevent the accidently contact.
CAUTION
•
Before operating high voltage wiring harnesses/connection, be sure to wear insulating
gloves and safety shoes.
•
Before connecting the power output cable and performing subsequent power cable
operations, make sure that the PDU switch is off.
•
The positive and negative poles of each module are marked, Exercise extreme caution to
prevent the wrong connecting.
•
Be aware of avoiding touching the modules positive and negative terminals with the
Figure48 Modules Communication cables