EN
43
8.2 Cleaning
Clean the regenerative container with drinking water if it is dirty.
For hygienically demanding applications
Twice a year
For standard applications
Once a year
8.3 Disinfection
For Rondomat DVGW only:
Disinfection if not used for more than 4 days
8.4 Power failure
If there is an extended power failure (8 hours), the unit starts operation
with a regeneration when the power returns.
If the power failure occurred during a regeneration, the controller rege-
nerates the column in which the regeneration process was interrupted
when power returns.
8.5 Shutting down
BWT drinking water softening units are produced and supplied hygie-
nically. After start-up the ion exchanger resin tends to become infected
if shut down incorrectly and therefore to release organic substances.
Therefore, the procedure described below is required under the follo-
wing conditions:
If no water is available for more than 48 h (e.g. for modifications, the sof-
tening unit is disconnected from the drinking water network).
If the softening unit is not required for an extended period (more than
4 weeks, e.g. seasonal operation in a hotel).
Ideally, the softened water supply should be almost completely used up
before shutting the unit down.
The columns should only being flushed and not regenerated.
If this is not possible, the unit should be regenerated completely.
The water supply to the unit can now be shut off and the unit can be dis-
connected from the power supply.
8.6 Reactivating the unit
after shutting down
See the Start-up item
The unit must be completely regenerated anyway (both columns for
2 column units).
We recommend hygienic maintenance by our after-sales service team
after the unit is shut down.
Summary of Contents for Rondomat Duo-DVGW 10
Page 10: ...DE 10 6 1 Klemmenpläne Rondomat Duo DVGW 2 3 und Rondomat Duo Industrie 2 3 6 10 ...
Page 48: ...FR 48 ...
Page 70: ...70 ...