![BWT PERMAQ COMPACT 51 Installation And Operating Manual Download Page 7](http://html1.mh-extra.com/html/bwt/permaq-compact-51/permaq-compact-51_installation-and-operating-manual_2836822007.webp)
UK
7
51 it means that the permeate ca-
pacity us 6 % below the normal
160 l/h, i.e. 151 l/h. At the same
time make sure that the pressure
on the manometer (E-Figure 3)
does not exceed 15 bar incl. the
raw water pressure from the water
supply.
The normal pressure indicated on
the manometer in order to obtain
normal permeate capacity will be
approx. 13.5-14.5 bar.
When the requested pressure and
permeate capacities have been ob-
tained, check again if the outlet
amount has been adjusted correct-
ly.
When both valves have been ad-
justed, they shall be locked with the
lock nuts. Please take care not to
move the valve when you tighten
the lock nut.
NB! When the valves have been
locked, the plant shall be started
and stopped 4-5 times, and then
the flow shall be checked again;
the valves are re-adjusted if neces-
sary.
Now check that the quality of the
treated water on the permeate
hose (A-Figure 3); the conductivity
shall be below 20 µS/cm (conduc-
tivity meter is available as accesso-
ry). If the water quality is below 20
µS/cm it is OK and the hose can
be led back to the hole in the res-
ervoir tank.
The 50 litre reservoir tank now will
be filled up with treated water <20
µS/cm.
Write the operating data in the en-
closed operating journal (see sec-
tion – 13.5 Operating journal).
7.3
Start of transport
pump
The transport pump (G-Figure 3) is
controlled by a pressure switch and
hydrophore is preset to 2.7 bar
from our factory, so they do not
have to be adjusted.
Note! The transport pump (G-
Figure 3) will not start until the res-
ervoir tank has been completely
full. Wait for the reservoir tank to
fill up completely (approx. 20
minutes). Check that the level
switch (H-Figure 3) automatically
stops the plant when the reservoir
tank is full.
NB: Do not touch the level switch.
Create a large consumption of
treated water to get the air out of
the pump.
Check that the transport pump (G-
Figure 3) starts up automatically.
Check that the pump supplies wa-
ter and pressure.
When you have checked the
transport pump and found it to be
in order, close for consumption of
treated water.
Wait for the transport pump to stop
automatically.
Note! The transport pump does not
stop until 20/30 seconds after the
consumption has ceased due to the
built-in delay in the control box.
Once again create a consumption
of treated water and this time let
the transport pump (G-Figure 3)
empty approx. 25 litres of the res-
ervoir tank content. Check if the
plant starts up automatically and
produces treated water. This can
be read on the flow meter (F-Figure
3).
The plant is now commissioned
and ready for use.
7.4
Use of by-pass
Furthermore the plant is furnished
with a manual by-pass for raw wa-
ter, i.e. if the plant for some reason
experiences
disturbances,
this
valve can be opened and you will
have raw water on the outlet for
consumption. IMPORTANT! When
the plant is restarted, you must re-
member to close the by-pass valve
again, otherwise you will get a
mixture of permeate and raw wa-
ter on the outlet.
8.
AUTOMATIC
FUNCTIONS
The BWT PERMAQ
®
Compact 51
plant is equipped with a control
box which has following built-in
control functions:
Level switch for start/stop
of high-pressure pump
Indication of low level and
stop of transport pump
Solenoid valve controls
raw water inlet
Pressure
switch
for
start/stop transport pump
(Stop 4.0 bar, Start 3.0
bar)
Alarm will go off when
raw water pressure drops
below 0.5 bar for more
than 2 min
Alarm will go off if
transport pump has been
running for more than 20
min
Stop of pump is delayed
by 20/30 seconds.
Extra level switch, “Alarm:
High level” (Option).
Alarm conditions and DIP-
switch, se section 9.2.10
and 9.2.11.
Summary of Contents for PERMAQ COMPACT 51
Page 2: ...UK 2...
Page 10: ...UK 10 9 2 3 Alarm Low raw water pressure 9 2 4 Alarm Transport pump...
Page 11: ...UK 11 9 2 5 Indication Level low 9 2 6 Alarm Level high...
Page 12: ...UK 12 9 2 7 The plant is not operating...
Page 20: ...UK 20 13 1 P I Diagram...
Page 21: ...UK 21 13 2 Layout Drawings...
Page 22: ...UK 22...
Page 23: ...UK 23...
Page 24: ...UK 24...
Page 25: ...UK 25 13 3 Wiring Diagrams...
Page 26: ...UK 26...
Page 27: ...UK 27...
Page 32: ...UK 32 13 7 Spare Parts Drawing...