7 | Parameter Description
28 / 44
0870208958_INVEOR_VFD_-0002_PCI_en
4.034 AI1 physical minimum
Selection of the lower limit of a physical value to be displayed:
0 = default value to be adapt to your process
4.035 AI1 physical maximum
Selection of the upper limit of a physical value to be displayed:
100 = default value to be adapt to your process
7.6.3.2 Current Input
1.100 Operating mode
Selecting the operation mode, following software enabling (1.131) and hardware en-
abling, the drive controller runs as follows:
0 = frequency setting mode, with the target value of the selected target value source
1.130
1.130 Target value source
Determines the source from which the target value is to be read:
1 = analogue input 1
4.020 AI1 input type
Function of analogue input 1:
2 = current input
4.021 AI1 standard Low (%)
Specifies the minimum value of the analogue inputs as a percentage of the range:
Example:
0 … 20 mA
►
0% … 100%
4 … 20 mA
►
20% … 100%
0
►
0 mA
►
0% = default value to be adapt to your process
4.022 AI1 standard High (%)
Specifies the maximum value of the analogue inputs as a percentage of the range:
Example:
0 … 20 mA
►
0% … 100%
4 … 20 mA
►
20% … 100%
100
►
20 mA
►
100% = default value to be adapt to your process
4.023 AI1 dead time (%)
Dead time as percentage of the range of the analogue input:
0 = no dead time default value to be adapt to your process
4.024 AI1 filter time (second)
Filter time of analogue inputs in seconds:
0.02 = default value to be adapt to your process
4.030 AI1 function
Function of analogue input 1:
0 = analogue input