PART 3-INSTALLATION AND MAINTENANCE
The following list should be checked after any installation is complete. If
possible, these types of checks should be assisted by a qualified person other
than the persons that performed the installation.
•
All holes in bottom of 1100 enclosure have been sealed to dust,
obtrusive objects and fingers.
•
Unused wires have been protected and insulated according to local
standards.
•
Electrically live parts are all protected from access by enclosures or
barriers.
•
No loose or missing parts, including screws, especially 1100 front
panel screws.
•
Burny has been informed of all problems with the hardware.
•
Environment within Burny operation specifications.
•
Away from sources of moisture.
•
Equipment away from combustible vapors and gases.
•
Equipment adequately distanced from high- heat sources.
•
Area dust and particulate level satisfactory.
•
Operator and equipment away from areas where objects fall, slide, roll,
etc.
•
Operator's view of work and equipment satisfactory.
•
Operator and equipment out of way of travel.
•
Cables routed to avoid damage after the installation.
•
No excessive cramping or stretching of cables.
•
Rear panel of unit accessible enough to see and to change cables.
•
Operator not subjected to unsafe or unnecessarily stressful conditions.
•
Wire size for AC and DC mains should be AWG 18 or larger.
•
Each cable is supplied by, designed by, or approved by Burny
•
The system and all other electrical devices associated with and in the
proximity of the system have been properly grounded.
•
Both ends of every cable have a ground clamp attached snugly to the
cable shield.
•
Every ground clamp is attached to its component enclosure in the
proper manner.