Summary of Contents for V11 Series

Page 1: ... r e s r o F l e b a L g n i t a R n o n w o h s s a r e b m u N l a i r e S d n a r e b m u N l e d o M r e l i o B e d i v o r p r e l i o b r e b m u N l e d o M r e l i o B r e b m u N l a i r e S r e l i o B e t a D n o i t a l l a t s n I _ _ _ 1 1 V _ _ _ _ _ _ _ 4 6 r o t c a r t n o C g n i t a e H g n i r i F e p y T s s e r d d A r e b m u N e n o h P Commercial Boilers www burnhamcomme...

Page 2: ... ...

Page 3: ...mended Installation Practices B The equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment CSA B149 and applicable Provincial Regulations for the class which should be carefully followed in all cases Authorities having jurisdiction should be consulted before installations are made C All wiring on boilers installed in Canada shall be m...

Page 4: ...II of this manual for details This boiler is suitable for installation on combustible flooring Do not install boiler on carpeting Do not operate on floors where heat affected material is below Do not tamper with or alter the boiler or controls Retain your contractor or a competent serviceman to assure that the unit is properly adjusted and maintained Clean boiler at least once a year preferably at...

Page 5: ...ury or loss of life to vent safely and will contribute toward maintaining the boiler s efficiency This boiler is supplied with controls which may cause the boiler to shut down and not re start without service If damage due to frozen pipes is a possibility the heating system should not be left unattended in cold weather or appropriate safeguards and alarms should be installed on the heating system ...

Page 6: ...llation 33 Package Boilers Preparation for Installation 33 Common Installation Requirements Boiler Piping Heating Applications 34 Boiler Piping Steam Applications 42 Boiler Piping Domestic Hot Water DHW Applications 44 Tankless Heater Piping 45 Electric Wiring 46 SECTION IV OPERATING INSTRUCTIONS Filling System 50 Adjusting Controls 50 Adjusting Burner 51 Test Controls 51 Initial Cleaning Steam Bo...

Page 7: ...I 57 Power Flame Burners Table VII 58 Webster Burners Table VIII 61 Carlin Burners Table IX 64 SECTION VII REPAIR PART Regional Office Directory 65 Jacket Assembly 66 Bare Boiler Assembly 70 Steam Water Trim 74 WARRANTY Rear Cover TABLE OF CONTENTS Continued ...

Page 8: ... SECTION I GENERAL INFORMATION Figure 1 Dimensional Information ...

Page 9: ...6 857 2679 643 745 7 4 1068 83 5 96 2 10 6 0 36 68 84 3076 3210 8 V1106 31 9 1069 3342 802 930 9 2 1328 102 4 118 0 13 2 0 37 77 96 3561 3720 8 V1107 38 3 1281 4013 963 1114 11 0 1588 121 3 198 8 15 9 0 42 87 108 4050 4225 10 V1108 45 3 1517 4829 1159 1319 13 0 1876 140 2 161 6 18 5 0 42 96 120 4533 4733 10 V1109 51 7 1729 5563 1335 1503 14 8 2136 159 1 183 4 21 1 0 39 105 132 5022 5247 10 V1110 5...

Page 10: ...s Tankless Heater Provide a minimum clearance from boiler jacket of 12 With Tankless Heater Provide a minimum clearance from the boiler jacket of 35 for installation and removal of tankless heater s TOP Provide a minimum clearance from the boiler jacket of 24 2 FOR MINIMUM CLEARANCES to combustible materials See Table II 3 PROVIDE ADEQUATE FOUNDATION for the unit Refer to Figure 2 e u l F t e l t ...

Page 11: ... the authority having jurisdiction a In the absence of local requirements the confined space shall be provided with two permanent openings one in or near the top of the room and one near the bottom The openings shall communicate by means of ducts with the outdoors or to such spaces crawl or attic that communicate with the outdoors i Where communicating by means of vertical ducts each opening shall...

Page 12: ...n monoxide from the joints on these materials and can result in severe personal injury or death Installations having long horizontal runs or an excessive amount of tees or elbows will restrict the flow of combustion gases and can result in condensation flue gas leakage of carbon monoxide resulting in severe personal injury or death WARNING When a V11 gas fired boiler is connected to a venting syst...

Page 13: ...proper vent is suspected remove pipe at breeching and operate boiler This will determine if excessive down draft blocked or restricted flue etc is causing the problem 2 If using type shown in A above be sure cap is raised sufficiently above main pipe to allow flue gases to vent unimpeded 3 A popular type cap is shown in B 4 The tee is frequently used as shown in C 5 D and E should not be used due ...

Page 14: ...D SECTIONS If the boiler was ordered to be field assembled follow the assembly procedure outlined on the following pages 1 ASSEMBLY OF SECTIONS MANUAL DRAW UP These sections are designed to be drawn together one section at a time using the 11 long draw up rods provided and ordinary hand tools Tools required 1 Drive Ratchet 1 1 Socket 1 1 Combination or Open End Wrench 1 Can Thread Cutting Oil or G...

Page 15: ...od with the hammer WARNING Nipples must be driven in evenly and to the proper depth to assure tight joints Most nipple leaks are caused by tilted or cocked nipples DO NOT use steel iron head hammer to drive nipples without using a wood block Nipple damage may result g A special nipple setting gauge is provided for the nipples Gauge nipple at 90 angles to insure that it is driven to the proper dept...

Page 16: ...X u CT C u CT B V1117 F C uCT C u CT CXl u C C Cn C u CT CX u CT C u CT C B V1118 F C uCT C u CT CXl u C C Cn CX u CT C u CT CX u CT C u CT B V1119 F C uCT C u CT CXl u C C CT CX u Cn C u CT CX u CT C u CT C B V1120 F C u CT C u CT CXl u C C CT CX u Cn C u CT C u CT CX u CT C u CT B V1121 F C uCT C u CT CXl u C C CT CX u Cn C u CT C u CT CX u CT C u CT C B V1122 F C uCT C u CT CXl u C C CT CX u Cn...

Page 17: ...r crowbar under the center of the section and lift the nipple port onto the upper nipple Drive section in place with a heavy block of wood striking blows as squarely as possible over nipple ports k Large draw up rod lugs with dual holes are cast in thefourcornersofeachcasting STARTING WITH THE UPPER HOLES install four 3 4 x 11 long draw up rods along with washers and nuts see Figure 9 CAUTION To a...

Page 18: ...T to the grooves in the ground joints between adjacent sections as the boiler operates with a positive pressure in the firebox and products of combustion will escape between sections unless they are properly sealed The rope and sealant should be applied before each section is placed on the assembly Figure 10 Jacket Intermediate Panel Mounting Brackets Required on Boiler Models V1113 thru V1123 Fig...

Page 19: ...ween adjoining sections should be spaced 1 4 to 3 8 apart Spacing of more than 3 8 will limit number of sections that can be drawn up in one unit and could indicate cocked nipples WARNING Sealant must be properly applied to ALL grooves Failure to properly seal the boiler joints will result in combustion gas leaks through the joint DO NOT operate boiler with combustion gas leaks The sealant should ...

Page 20: ...t Support Brackets must be attached to the appropriate center section during this process Check Section Arrangement chart for location of center section to which jacket support brackets must be attached see Figure 8 i LOCATE JACKET INTERMEDIATE PANEL MOUNTING BRACKETS NO 1 NO 2 AND NO 3 IN JACKET CARTON Brackets are shipped flat and must be formed by hand bend as shown in Figure 10 Brackets are sh...

Page 21: ...psig WARNING Failure to properly hydrotest all boilers at the correct pressure may result in section assembly failure in operations 4 EXAMINE BOILER CAREFULLY INSIDE AND OUTSIDE to insure against leaks from cocked nipples or through concealed breakage caused in shipping and handling This precaution is for your protection and will simplify handling of necessary replacements and adjustment claims 5 ...

Page 22: ...22 SECTION III INSTALLATION INSTRUCTIONS Figure 15 Bare Boiler Assembly NOTE Flue top insulation not shown ...

Page 23: ...flush with raised flange on back section Tighten rear set of canopy J bolts only 10 Open either the rear flue outlet carton standard or top flue outlet carton optional 11 Attach the 1 8 x 1 wide self adhesive fiber gasket to the surface of either the rear flue outlet damper assembly or rear flue outlet cover that mounts against the canopy and back section Gasket must be centered over all attachmen...

Page 24: ... Long sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separately from other laundry and rinse washing machine after use to avoid contaminating other clothes Discard used RCF components by sealing in an airtight plastic bag RCF and crystalline silica are not clas...

Page 25: ... 6 for mounting remaining flue cover plates C MOUNT REAR OBSERVATION PORT COVER Refer to Figure 15 1 Apply a bead of Silastic sealant along the groove on the inside face of the rear observation port cover 2 Mount the rear observation port cover onto the rear section with the word Top in the upright position using the 4 5 16 18 X 1 cap screws and washers provided D INSPECT SEALS 1 A visual inspecti...

Page 26: ...own until leg touches floor then add 1 2 to 1 full additional turn d Using two 2 sheet metal screws each attach the remaining U channels U side down between the tops of the front intermediate and rear jacket panels according to channel length 8 Position the loose piece of 1 thick x 36 wide fiberglass insulation provided in the canopy carton against left side U channel s across top of canopy and do...

Page 27: ...27 Figure 20 V11 Series Jacket Assembly Boiler Models V1104 Thru V1112 ...

Page 28: ...28 Figure 21 V11 Series Jacket Assembly Boiler Models V1113 Thru V1123 ...

Page 29: ...el No 2 Req d Rear U Channel No 4 Req d Rear J Channel No 2 Req d V1113 U46 J46 U34 J34 V1114 U46 J46 U40 J40 V1115 U46 J46 U46 J46 V1116 U52 J52 U46 J46 V1117 U52 J52 U52 J52 V1118 U52 J52 U58 J58 V1119 U65 J65 U58 J58 V1120 U65 J65 U58 J58 V1121 U65 J65 U65 J65 V1122 U65 J65 U71 J71 V1123 U65 J65 U77 J77 Left Side Usage Chart Boiler Size Single Left Side Panel Multiple Side Panels Front to Rear ...

Page 30: ...eet metal screws 14 Tighten all sheet metal screws to complete jacket assembly G MOUNT BURNER MOUNTING PLATE refer to Figures 15 and 26 1 Install ten 10 5 16 x 2 long tap end studs with the short length of threads into the boiler front section 2 With the use of silastic secure the 3 16 diameter rope gasket to the groove along the mounting plate opening in the front section 3 Place burner mounting ...

Page 31: ...eater repair and replacement also for the removal of jacket right side panels for boiler repair and inspection Therefore the recommended use and placement of shut off valves and unions on all manifold assemblies is crucial to providing easy access for future servicing I STEAM BOILERS INSTALL STEAM TRIM Items for steam trim are located in the steam trim carton except for the separately ordered low ...

Page 32: ...32 Figure 28 Minimum Piping Recommendations for V11 Series Tankless Heater Manifolds ...

Page 33: ...odes say otherwise All controls are pre wired down to the burner If burner is equipped with a lead lag panel lead lag controls will be shipped loose for header mounting The power can be supplied to the burner if equipped with a control panel If burner has no panel the power is supplied to the J box on the front jacket 2 SUPPLY CONNECTIONS Removal of top jacket is not required to connect the supply...

Page 34: ... adjustments should be made once the unit is installed and adjusted M BOILER PIPING HEATING APPLICATIONS Connect supply and return piping to heating system see Figures 31 to 37 Flow direction for hot water boilers must be from the rear return out through the top front supply Steam boilers can pipe return to the front as an alternate location Some boiler sizes may require the use of additional supp...

Page 35: ...er circulator will maintain a constant flow through the boiler during every heat demand while the by pass diverts a portion of hot water back to the return Alternate minimum multiple boiler piping is shown in Figure 36 The blend pump will maintain constant flow through the boiler during every heat demand and provide a hot water blend back to the return f Glycol Antifreeze Solutions Many systems to...

Page 36: ...36 Figure 31 V11 Series Minimum Piping Recommendation Parallel Water ...

Page 37: ...37 Figure 32 V11 Series Minimum Piping Recommendation Primary Secondary Water ...

Page 38: ...38 Figure 33 Minimum Piping Details Bypass With Blend Pump ...

Page 39: ...39 Figure 34 Minimum Piping Details Primary Secondary Piping With Bypass ...

Page 40: ...40 Figure 35 Minimum Piping Details Multiple Boiler Application Primary Secondary Piping With Bypass ...

Page 41: ...41 Figure 36 Minimum Piping Details Multiple Boiler Application Parallel Piping With Blend Pump ...

Page 42: ...ow at header connection 3 Ball valve preferable gate valve acceptable alternative supplied by others Minimum valve size per ASME code is 1 NPT V1104 1106 1 1 4 NPT V1107 1112 1 1 2 NPT V1113 1123 Increasing the valve size will improve the blowdown operation In all cases piping connecting blowoff valve to boiler shall be full size to the point of discharge 4 Header piping may be run over the top of...

Page 43: ...43 Figure 38 Typical Steam Piping Arrangement for Boilers with Pumped Condensate Return and Boiler Feed Unit ...

Page 44: ... use of several tankless coils piped in parallel emptying into a large storage tank and is typically used in larger DHW production applications such as hotel showers and laundries See Figure 42a for recommended piping and wiring details for this type of application The tempering valve and recirculation loop are advantageous in these applications because they provide both high temperature and tempe...

Page 45: ... is not subjected to excess temperatures that may occur during off periods when it is possible for heat to be conducted back through the supply line The flow regulator also limits the flow of supply water regardless of inlet pressure variations in the range of 20 to 125 psi Figure 41 Schematic Tankless Heater Piping Table V Tankless Heater Ratings 2 Tempering of Hot Water WARNING Install a mixing ...

Page 46: ...ter This is applicable to some city water and particularly to well water An appropriate water softener should be installed based on the analysis and dealer s recommendation This is not only beneficial to the tankless heater but to piping and fixtures plus the many other benefits derived from soft water P INSTALL ELECTRIC WIRING in accordance with National Electric Code and local regulations A sepa...

Page 47: ...47 Figure 42a DHW Generation with Tankless Coils Storage Tank and Destratification Pump ...

Page 48: ...48 Figure 42b DHW Generation with Indirect Water Heater ...

Page 49: ...49 Figure 43 Steam Boiler Safety Valve Hook Up Figure 44 Water Boiler Pressure Relief Valve Hook Up ...

Page 50: ... normal system design operating pressure Close fill valve Note If make up water line is equipped with pressure reducing valve system will automatically fill to normal system design operating pressure Leave globe valve open j Open isolation valve in boiler supply piping k Remove hose from hose bib DANGER Do not operate boiler with pressure above maximum allowable working pressure listed on the Boil...

Page 51: ...ankless heaters With burner off draw hot water until burner starts then turn off hot water and check burner shutdown F BOILER AND SYSTEM CLEANING STEAM BOILER NOTICE A qualified water treatment chemical specialist should be consulted for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations WARNING Chemicals used in tr...

Page 52: ...ining the boiler and return main and refilling the boiler until sample is clear f If the boiler water becomes dirty again at a later date due to additional sediment loosened up in the piping close gate valve in Hartford Loop open drain valve in return main turn on burner and allow condensate to flow to drain until it has run clear for at least 30 minutes while feeding water to boiler so as to main...

Page 53: ...s a gas Both can result in reduced boiler life The accumulation of sediment can eventually isolate the water from contacting the cast iron When this happens the cast iron in that area gets extremely hot and eventually cracks The presence of free oxygen in the boiler creates a corrosive atmosphere which if the concentration becomes high enough can corrode the cast iron through from the inside Since...

Page 54: ...OX a Disconnect fuel line s and remove burner and burner mounting plate b Using wire or fibre bristle brush clean crown of boiler and inside of water legs c Inspect firewall plates for damage or deterioration Replace as needed per instructions outlined in Section III Paragraph E DANGER This boiler used flammable gas high voltage electricity moving parts and very hot water under high pressure Assur...

Page 55: ...ders should be dismantled annually by qualified personnel to the extent necessary to insure freedom from obstructions and proper functioning of the working parts Inspect connecting lines to boiler for accumulation of mud scale etc and clean as required Examine 5 REASSEMBLE BOILER CAUTION Do not start the burner unless canopy smokepipe burner mounting plate and all flue plates are secured in place ...

Page 56: ...tor open vent until water escapes and then close 3 If much water is added to system it is advisable to heat system to a high temperature and vent again This will make less venting necessary during the winter 4 Where an expansion tank is used make sure that neither the tank nor its drain pipe is exposed to freezing temperatures Never place valves in piping leading to or from expansion tank 5 Boiler...

Page 57: ...4 0 6 0 150 300 Hago 10 50 x 45 P V1112 20 0 Beckett CF2500 CF66KP 4 1 5 4 5 300 300 Hago L 5 50 x 45 P H 5 50 x 45 P V1113 21 5 Beckett CF2500 CF66KP 5 1 0 5 5 300 300 Hago L 6 00 x 45 P H 6 00 x 45 P V1114 23 5 Beckett CF3500A CF80KH 2 2 0 8 0 300 300 Hago L 6 50 x 45 P H 6 50 x 45 P V1115 25 5 Beckett CF3500A CF80KM 3 1 5 9 0 300 300 Hago L 7 00 x 45 P H 7 00 x 45 P V1116 27 0 Beckett CF3500A C...

Page 58: ...100 300 Delavan 10 0 x 80 33769 V1112 20 0 Power Flame CR3 O 1 4 3 16 3 16 1 1 4 1 1 4 100 280 Delavan 12 0 x 80 33769 V1113 21 5 Power Flame CR3 O 1 4 3 16 3 16 1 1 2 1 1 2 100 300 Delavan 12 0 x 80 33769 V1114 23 5 Power Flame CR3 O 1 4 1 4 1 4 1 3 4 1 3 4 100 300 Delavan 16 0 x 80 33769 V1115 25 5 Power Flame CR3 O 3 8 1 4 1 4 1 7 8 1 7 8 100 285 Delavan 16 0 x 80 33769 V1116 27 0 Power Flame C...

Page 59: ...lame CR3 G 20 3 8 1 2 1 2 1 3 4 1 1 2 3 2 5 8 1 1 8 V1112 2887 Power Flame CR3 G 20 1 4 3 16 3 16 1 1 4 1 1 4 2 9 6 0 1 1 4 V1113 3103 Power Flame CR3 G 20 1 4 3 16 3 16 1 1 2 1 1 2 3 2 6 8 1 1 4 V1114 3392 Power Flame CR3 G 20 1 4 1 4 1 4 1 3 4 1 3 4 3 1 7 4 1 3 8 V1115 3680 Power Flame CR3 G 20 3 8 1 4 1 4 1 7 8 1 7 8 2 2 7 3 N A V1116 3897 Power Flame CR3 G 25 3 16 1 8 1 8 1 1 4 1 1 4 3 0 6 6 1...

Page 60: ...1 1 2 3 2 5 8 1 1 8 V1112 20 0 2887 Power Flame CR3 GO 20 1 4 3 16 3 16 1 1 4 1 1 4 2 9 6 0 1 1 4 V1113 21 5 3103 Power Flame CR3 GO 20 1 4 3 16 3 16 1 1 2 1 1 2 3 2 6 8 1 1 4 V1114 23 5 3392 Power Flame CR3 GO 20 1 4 1 4 1 4 1 3 4 1 3 4 3 1 7 4 1 3 8 V1115 25 5 3680 Power Flame CR3 GO 20 3 8 1 4 1 4 1 7 8 1 7 8 2 2 7 3 N A V1116 27 0 3897 Power Flame CR3 GO 25 3 16 1 8 1 8 1 1 4 1 1 4 3 0 6 6 1 1...

Page 61: ...O 10 3 8 0 015 5 16 7 8 1 1 8 100 286 Delavan 2 5 50 x 80 B V1112 20 0 Webster JB2O 10 3 8 0 015 5 16 3 4 1 1 4 100 292 Delavan 2 6 00 x 80 B V1113 21 5 Webster JB2O 10 3 8 0 015 5 16 3 4 1 1 4 100 287 Delavan 2 6 50 x 80 B V1114 23 5 Webster JB2O 10 3 8 0 015 5 16 3 4 1 1 4 100 294 Delavan 2 7 00 x 80 B V1115 25 5 Webster JB2O 10 3 8 0 015 5 16 1 1 8 1 3 4 100 300 Delavan 2 7 50 x 80 B V1116 27 0...

Page 62: ...Webster JB1G 07 1 4 1 8 1 4 3 4 1 1 16 3 1 V1111 2656 Webster JB2G 10 3 8 0 015 5 16 7 8 1 1 8 2 4 V1112 2887 Webster JB2G 10 3 8 0 015 5 16 3 4 1 1 4 2 6 V1113 3103 Webster JB2G 10 3 8 0 015 5 16 3 4 1 1 4 2 9 V1114 3392 Webster JB2G 10 3 8 0 015 5 16 3 4 1 1 4 3 2 V1115 3680 Webster JB2G 10 3 8 0 015 5 16 1 1 8 1 3 4 3 7 V1116 3897 Webster JB2G 15 5 16 0 015 1 2 7 8 1 1 2 4 0 V1117 4186 Webster ...

Page 63: ...bster JB2C 10 3 8 0 015 5 16 7 8 1 1 8 2 4 100 286 Delavan 2 5 50 x 80 B V1112 20 0 2887 Webster JB2C 10 3 8 0 015 5 16 3 4 1 1 4 2 6 100 292 Delavan 2 6 00 x 80 B V1113 21 5 3103 Webster JB2C 10 3 8 0 015 5 16 3 4 1 1 4 2 9 100 287 Delavan 2 6 50 x 80 B V1114 23 5 3392 Webster JB2C 10 3 8 0 015 5 16 3 4 1 1 4 3 2 100 294 Delavan 2 7 00 x 80 B V1115 25 5 3680 Webster JB2C 10 3 8 0 015 5 16 1 1 8 1...

Page 64: ... V1109 14 8 Carlin 801CRD 97980 3 4 1 2 150 150 Hago 2 6 00 x 45 H V1110 16 6 Carlin 1050FFD 97981 1 4 1 8 100 100 Hago 1 9 00 2 3 75 x 45 SS V1111 18 4 Carlin 1050FFD 97981 7 16 11 16 100 100 Hago 1 9 00 2 4 50 x 45 SS V1112 20 0 Carlin 1050FFD 97981 3 8 9 16 100 100 Hago 1 9 00 2 5 50 x 45 SS V1113 21 5 Carlin 1050FFD 97981 9 16 1 2 100 100 Hago 1 9 00 1 6 50 1 6 00 x 45 SS V1114 23 5 Carlin 115...

Page 65: ...ugh your local Burnham Wholesale Distributor Should you require assistance in locating a Burnham Distributor in your area or have questions regarding the availability of Burnham products or repair parts please contact Burnham Customer Service at 717 481 8400 or Fax 717 481 8408 ...

Page 66: ...66 Figure 45 V11 Series Jacket Assembly Boiler Models V1104 Thru V1112 ...

Page 67: ...080 6F Jacket Top Panel Assembly V1109 1 60426090 6G Jacket Top Panel Assembly V1110 1 60426100 6H Jacket Top Panel Assembly V1111 1 60426110 6 I Jacket Top Panel Assembly V1112 1 60426120 7 Jacket Single Left Side Panel Assemblies 7A Single L S Pnl Assy No SLS24 1 60426043 7B Single L S Pnl Assy No SLS30 1 60426053 7C Single L S Pnl Assy No SLS36 1 60426063 8 Jacket Forward Left Side Panel Assemb...

Page 68: ...68 Figure 46 V11 Series Jacket Assembly Boiler Models V1113 Thru V1123 ...

Page 69: ...9C Jacket Rear Top Panel Assy V1115 1 60426154 9D Jacket Rear Top Panel Assy V1116 1 60426164 9E Jacket Rear Top Panel Assy V1117 1 60426174 9F Jacket Rear Top Panel Assy V1118 1 60426184 9G Jacket Rear Top Panel Assy V1119 1 60426194 9H Jacket Rear Top Panel Assy V1120 1 60426204 9 I Jacket Rear Top Panel Assy V1121 1 60426214 9J Jacket Rear Top Panel Assy V1122 1 60426224 9K Jacket Rear Top Pane...

Page 70: ...70 Figure 47 Bare Boiler Assembly NOTE Flue top insulation not shown ...

Page 71: ...22 24 26 28 30 32 34 36 38 40 42 44 80861680 14 Tankless Heater Cover Plate Gasket One Required for each CT Section 8032601 15A V11 2 Tankless Heater Assembly One Required for each CT Section 6032601 OR 15B Blank Heater Cover Plate Only One Required for each CT Section 6032602 16 Rear Observation Port Cover Incls gasket mounting hdwe 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 609600011 17 Canopy Asse...

Page 72: ...72 Figure 47 Bare Boiler Assembly ...

Page 73: ...36 28B Shutter Handle 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8026033 28C Shutter Spring 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8026034 28D Observation Port Shutter Machined painted 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 70260051 28E Spring Pin 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8026035 29 Observation Port Asssembly Parts 29A Observation Port Cover Machined Painted 1 1 1 1 1 1 1 1 1 1 1 1 1...

Page 74: ...3501 Pipe Plug 3 NPT Square Head Black 1 1 1 1 1 1 806603514 Lowest Permissible Water Level Plate Form No 1204A 1 1 1 1 1 1 81460009 WATER TRIM V1104 7 V1108 11 V1112 20 V1121 23 PART NO Aquastat Controller Honeywell L4006A2015 1 1 1 1 80160400U Immersion Well Honeywell 123871A NPT 1 1 1 1 80160452 Temperature Pressure Gauge 100 PSI 80 320 F NPT 1 1 1 1 8056028 Relief Valve Piping Hex Bushing 3 NP...

Page 75: ...75 SERVICE RECORD DATE SERVICE PERFORMED ...

Page 76: ...satisfactory performance as a result of faulty workmanship in the installation which liability is expressly disclaimed e Boilers parts or accessories installed outside the 48 contiguous United States the State of Alaska and Canada f Damage to the boiler and or property due to installation or operation of the boiler that is not in accordance with the boiler installation and operating instruction ma...

Reviews: