INSTRUCTIONS FOR THERMOWELD GROUNDING CONNECTIONS - ACR-1, ACR-2 & AR-1 TYPE MOLDS
ACR-2
Place cable and ground rod into mold. Insert
ground receptacle into mold. Use a pair of
locking pliers or a clamp to prevent mold
from slipping when fired.
AR-1
Place mold onto ground rod. Next
place ground receptacle into mold.
There should be approximately 1/8"
between end of ground rod and end
of receptacle. Use a pair of locking
pliers or a clamp to prevent mold
from slipping when fired.
ACR-1
Place cable and ground rod into mold. End
of cable should be to center of ground rod.
Insert ground receptacle into mold. Use a
pair of locking pliers or a clamp to prevent
mold from slipping when fired.