.6 default settings of the calibration mode
Ex works the settings of the Calibration Mode are:
Pressure unit:
bar
Transistor outputs (*):
hysteresis
OLO1 and 2 (*):
-0,2 bar (range 0-2); -0,5 bar (range 0-5); -1 bar (range 0-10);
-2 bar (range 0-20); -5 bar (range 0-50)
OHI1 and 2 (*):
max. of the range
INV1 and 2 (*):
no
DEL1 and 2 (*):
0 s
Filtre:
0, FAST
4 mA:
0 bar
20 mA:
max. value of the measuring range
BGLO:
0 bar
BGHI:
max. value of the measuring range
FAIL:
CONT (continue), for OUT1 and OUT2
22 mA, for the 4-20 mA output
CODE:
OFF (not used), value 0000
(*) Only versions with transistor outputs