48
Electrical installation
Type 8098 FLOWave L
8.5
Activating the device internal termination resistor
The device has an internal termination resistor that can be activated if the device is installed at one end of a
büS network or of a CANopen network.
If you activate the device internal termination resistor, do not install more than one termination resistor at the
same end of the büS network or of the CANopen network.
To have an adapted network, connect one termination resistor at each end of the network.
→
Go to the
CONFIGURATION
view.
→
General settings
→
Confirm to access the
Parameter
view.
→
büS
→
Advanced
Termination resistor
→
On
→
Save.
The internal termination resistor is activated.
8.6
Specifications of the cables for the M20x1.5 cable
glands (device variant with cable glands)
Table 13:
Specifications of the cables for the M20x1.5 cable glands in nickel plated brass
Specification of the cables
Recommended value
Electromagnetic protection (EMC)
Shielded
Diameter
5...14 mm
Maximum operating temperature
80 °C or higher
Table 14:
Specifications of the cables for the M20x1.5 cable glands in stainless steel
Specification of the cables
Recommended value
Electromagnetic protection (EMC)
Shielded
Diameter
6...12 mm
Maximum operating temperature
80 °C or higher
8.7
Specifications of the conductors for the 12 push-in
terminal strip
Table 15:
Specifications of the conductors for the terminal strip
Specification of the conductors
Recommended value range
Cross section of a solid conductor H05(07) V-U
0.25...1.5 mm
2
Cross section of a stranded conductor H05(07) V-K,
with a wire ferrule but without collar
0.25...1.5 mm
2
Cross section of a stranded conductor H05(07) V-K,
with a wire ferrule with a plastic collar
0.25...0.75 mm
2
Cross section of other kinds of conductors
0.2...1.5 mm
2
(AWG24...AWG16)
English