Outputs – Parameter
Type 8098 FLOWave L
18.3.2
Choosing the damping level of the values transmitted on an
analogue output
The following diagram shows the effect of the damping on the flow rate measurements.
Volume flow rate measurement
The set damping level for the volume
flow rate measurements is applied
(see chapter 15.4.2
The resulting volume
flow rate is displayed.
The set damping level for the ana-
logue outputs is applied
If active, cut-off is applied.
The calculated volume
is used by the totalizers
and the pulse outputs.
The resulting volume flow rate value
is transmitted on the analogue
outputs
Fig. 67:
Effect of the damping on the flow rate measurements
When the damping is active (i.e. when a
Low
,
Medium
or
High
level has been set) and the values
vary for ±30 % (for example when charging the pipe or stopping the flow), the damping is not
applied to the new measured value.
Table 43:
Response times (10 %...90 %) of the damping levels
Damping level
Response time
None
< 1 s
Low
1 s
Medium
10 s
High
30 s
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...