202
SAW sensor – Parameter
Type 8098 FLOWave L
15.10
Setting the parameters of the volume totalizers
15.10.1
Giving a user defined name to each volume totalizer
The name is used to identify the process value in the user defined views and in all the menus where the
process value is displayed (for example in the
Outputs
menu).
By default, the names associated to the volume totalizers are
Totalizer 1
and
Totalizer 2
.
To add a user defined name to the default name of a volume totalizer, do the following:
→
Go to the
CONFIGURATION
view.
→
SAW sensor
→
Confirm to access the
Parameter
view.
→
Stand. meas. values
→
Totalizer 1
or
Totalizer 2
→
Value name
.
→
Enter the name by selecting and confirming each character. The name can have up to 19
characters.
→
OK
→
Save the name.
The name is changed.
15.10.2
Choosing the counting direction of each volume totalizer
By default, the counting direction of both volume totalizers is
Positive only
.
The possible counting directions are:
•
Positive only
: the volume totalizer counts the volume of liquid that flows in the direction defined as
positive, i.e. in the same direction as the arrow located on the front of the device.
•
Negative only
: the volume totalizer counts the volume of liquid that flows in the direction defined as
negative, i.e. in the direction opposite to the direction of the arrow located on the front of the device.
•
Both
: the volume totalizer counts the volume of liquid that flows in the direction defined as positive but
deducts the volume of liquid that flows in the direction defined as negative.
To change the counting direction of each volume totalizer, do the following:
→
Go to the
CONFIGURATION
view.
→
SAW sensor
→
Confirm to access the
Parameter
view.
→
Stand. meas. values
Totalizer 1
or
Totalizer 2
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...