51
Functions
10.2.9
OUTPUT
(variant) -
Configuring the analogue output (only for variants without
fieldbus communication)
The analogue output (
OUTPUT)
function only appears in the function selection if the positioner has an ana-
logue output (variant) or no parameters have been read in yet.
The analogue output can be used for feedback from the current position or from the set-point value at the
control centre.
Function Position (POS)
Issuing of the current position
Set-point value (CMD)
Issuing of the set-point value
Standard signal 4...20 mA
Selection of the standard signal
0...20 mA
10.2.10
Setting LED operation mode, device status
User level: installer
Factory setting: valve mode + warnings
Menu or function
Values or description
Device
>
General settings
>
Parameter
>
Status LED
Operation mode
NAMUR operation mode
Valve operation mode
Valve operation mode +
warnings
Fixed colour
LED off
Setting LED operation mode, device status:
→
Status LED
→
Operation mode
Possible selection:
NAMUR operation mode
Valve operation mode
Valve operation mode + warnings
Fixed colour
LED off
→
Choose operation mode.
The operation mode is set.
Type 8791, REV.2
english