![Burkert 8756 BATCH Operating Instructions Manual Download Page 33](http://html1.mh-extra.com/html/burkert-0/8756-batch/8756-batch_operating-instructions-manual_2832389033.webp)
Type 8756 BATCH
Setting and operation
33
Bit
Designation
Meaning
2
Dosing in progress
The product is dosing.
3
Ready - Start value is the set
opening time
The product is ready to dose and is waiting for the command
to start a dose. To perform the first dosing, the product uses
the set opening time of the valve.
4
Dosing in progress with the
set opening time as start value
The product is dosing and uses the set opening time of the
valve.
5
Trigger is impossible
The product is not ready to dose and cannot receive any start
command.
The produt cannot receive any start command in the following
situations:
▪
the actuator has been opened manually.
▪
an error has been generated (red or orange)
▪
the product is being initialized.
8.2.4.3
PDO2, Dosing information
The dosing information makes it possible to know whether a dosing has been performed successfully or
not.
Bit
Designation
Meaning
0
Maximum opening time is
reached
The maximum opening time during a dosing is reached.
1
Maximum balancing time is
reached
The maximum balancing time after a dosing is reached.
8.2.4.4
PDO2, Dosed quantity during last dosing
If large fluctuations occur in the dosed quantities, then remove possible environmental disturbances and
make sure the product is installed correctly.
8.2.4.5
PDO3, Error ID
Bit
Event
Product status indicator
0
Voltage warning
yellow
The supply voltage is outside the specification.
Operate the product within the specifications.
1
Voltage error
red
The supply voltage is outside the specification.
Operate the product within the specifications.
2
Product-temperature warning
yellow
The product temperature is outside the specification.
Operate the product within the specifications.