21
Technical data
Type 8746 Profibus, 8746 Analogue
6.5
Product materials
Tab. 8:
Product materials, common to all product variants
product part
material
Base block
•
Aluminium
•
Stainless steel 1.4305
Housing
Aluminium
Seal
Refer to the Type label
Product status indicator
Polycarbonate
Parts in contact with the
fluid (sensor)
1.4404, Al
2
O
3
, PPS GF40,
e
poxy
resin, silicon, silicon nitride
Tab. 9:
Specific materials of an MFC with proportional valve
Parts in contact with the
fluid
1.4310, 1.4113, 1.4305
Tab. 10: Specific materials of an MFC with motor valve
Parts in contact with the
fluid
1.4310, 1.4305, Al
2
O
3
, PPS GF40,
PEEK
Tab. 11:
Specific materials of an ATEX product variant
Impact protection-cover
Stainless steel 1.4301
6.6
Dimensions, weight
→
Refer to the data sheet of the related product.
6.7
fluid data
6.7.1
Mass flow Meter
Tab. 12:
Fluid data, MFM
Calibration fluid
Operating gas or air
Mass flow-rate range
(reference to N2 (I
N
/min))
20...2500 I
N
/min
Exact range depends on the product base-block size and on
the gas used. Refer to the datasheet related to the product
Type.
Measuring range
1:50
Larger measuring range
available on request.
Repeatability
±0.1% of the full scale
Operating fluid
See Type label
Measurement accuracy, after
15 minute warm-up time and
with the calibration fluid
± 1.5%
5)
of the measured value
± 0.3%
5)
of the full scale
Response time
< 500 ms
5) If the
operating fluid is different from the calibration fluid, then the
measurement accuracy can be lower. If the operating gas is nitrogen
or oxygen
, then
the given measurement accuracy is correct. But if the
operating gas is natural gas
, then the measurement accuracy may be
different
because the composition of natural gas varies depending on the
season and origin.