11
Description
Type 8746 Profibus, 8746 Analogue
5
descriPTiOn
5.1
Product variants
5.1.1
Mass flow Meter (MfM)
3
12
11
4
2
7
10
9
8
6
13
5
1
15
14
1.
Electrical connection:
-
Product variant Profibus: 5-pin M12 female connector, B
coding
-
Product variant Analogue: 5-pin M12 female connector, A
coding
2.
Electrical connection: 5-pin M12 male connector, A coding
3.
Possible fluid connections:
-
G-internal-threaded connections according to
DIN ISO 228/1
-
NPT-internal-threaded connections according to ASME/
ANSI B 1.20.1
-
flange connection
4.
M4 screw for functional earth connection
5.
Base block
6.
Flow direction
7. Product status indicator. The indicator operates according
to NAMUR NE 107.
8.
Not used
9.
Status LED for the fieldbus communication
10. Not used
11.
Cover
12.
M3 screw
13.
büS interface for the Bürkert Communicator software
14.
Slot for the memory card
15.
Impact protection-cover. The impact protection-cover is
only delivered with an ATEX product variant.
Fig. 1:
Product variants of a Mass Flow Meter