Pneumatic Installation
→
Connect the required
working connections 2/A1 to 2/A3
(according to the number of solenoid valves in
the control head) with the corresponding connections on the process valve (“Fig. 12”).
→
Connect the supply line to
supply pressure connection 1/P
(observe the permissible pressure range,
see chapter
NOTE!
Information to hose pipes!
• Only use approved hose pipes with Ø6 mm (or 1/4") or Ø8 mm (or 5/16") outer diameters (tolerance:
+0.05/-0.1 mm).
• Only use suitable hose qualities (in particular for high ambient temperatures) that bear up under common
stresses caused by the quick connector.
•
Only use a suitable hose cutter when cutting hose pipes. This will safeguard against damage and imper-
missible deformation.
•
Accordingly dimension hose length to prevent that the hose ends in the plug-in hose connectors generate
any diagonally pulling stresses (curved outlet without eccentric stress).
Application of silencer or exhaust air hose?
•
When using an exhaust air hose, accordingly dimension its length to ensure that a Q
Nn
value >620 l/min
is reached.
Note:
Dimension the hose lengths so that the control head can be removed from the process valve if
required without any additional disassembly work.
9.3
Flow restriction function of the solenoid valves
Set the flow restriction screws of the solenoid valves only when needed and after completion of all
necessary installations!
The flow restriction screws of the solenoid valves (see “Fig. 13”) are used for setting the air intake and
exhaust for the working connections and thus also for setting the opening and closing speed of the process
valve:
• Factory setting of nominal flow rate: Q
Nn
approx. 110 l/min.
• The flow restriction screws do not serve any sealing function.
• Only tighten the flow restriction screws to the stopper, otherwise damage to device may occur.
• Only use appropriate screwdrivers (b ≤ 3 mm).
When setting the retraction and extension rates of the pneumatic actuator, ensure that there is no
constant "primary pressure" during deaeration!
Keep in mind that the working conditions in the process valve area on the side of the product (flow
types, pressure variations) may result in changes in the set aeration and deaeration times.