132
Position Measuring System
20.2.2
Automatic Teach functions (Autotune)
The automatic Teach procedure of the valve positions S1 to S3 can be implemented using the automatic
Teach functions (Autotune).
The optical feedback
of the classic variants (24 V DC, 120 V AC, AS-i, DeviceNet) differ slightly
from those of the newer IO-Link and büS/CANopen variants.
This is due to the modified design of the top LED, which has been optimised for the display
according to “NAMUR” (NE 107, edition 2006-06-12).
The classic variants have 3 LEDs that can simultaneously display 3 colours (green, yellow, red).
The IO-Link and büS/CANopen variants have LEDs that can change their colour spectrum and are,
therefore, capable of display functions according to “NAMUR”.
Change to Autotune mode (mode to start the automatic Teach functions):
Teach button
Mode
Activation duration
Optical feedback
(classic designs)
Optical feedback
(IO-Link, büS/CANopen)
T2 + T3
Autotune-
Modus
2.5 s
green + red
all LEDs permanently ON
red + green
flashing in succession
(500 ms per colour)
Then one of the 6 automatic Teach functions (Autotune) can be selected according to the following table:
Teach button
Mode
Activation duration
Optical feedback
(classic designs)
Optical feedback
(IO-Link, büS/CANopen)
T1
Autotune 1
each 0.5 s
green + red
“running light”
(i.e. alternating display)
red + green
flashing in succession
(200 ms per colour
*)
)
T2
Autotune 2
T3
Autotune 3
T1 + T2
Autotune 4
T1 + T3
Autotune 5
T2 + T3
Autotune 6
The following applies to IO-Link and büS/CANopen devices:
*)
This optical feedback for
“automatic Teach function (Autotune) active”
is only valid for the display
mode
“Device-specific LED mode” (“8681 Classic 0 ... 15”)
- see chapter
With the other display modes
of the device status LED (top LED) – see chapter „21.1“ – there are diffe
-
rences in the colour and flashing pattern display for
“automatic Teach function (Autotune) active”.
See
also:
-
NAMUR mode
(chapter „21.1.2“) - display orange as a “function check”
-
Valve mode
(chapter „21.1.3“) - no display
-
Valve mode + error
(chapter „21.1.4“) - no display
-
Valve mode + error + warnings
(chapter „21.1.5“) - display orange as a “function check”
The following also applies to IO-Link-devices:
Following the procedure described above, a reference run is carried out during which the Teach positions
taught in the respective automatic Teach function (Autotune) are approached again one after the other. The
travel times are determined and stored as reference values in the Teach function.
Irregularities with the automatic Teach functions (Autotune)?
Refer to the notes below:
english
Control Head Type 8681
Summary of Contents for 8681
Page 165: ...165 english Control Head Type 8681 ...
Page 166: ...www burkert com ...