28
Installation
8.4.1
Connecting the control medium
→
Connect the control medium to the pilot air port (1) (3–7 bar;
instrument air, oil-/water-/dust-free).
→
Mount the exhaust air line or a silencer onto the exhaust air port
(3) and, if available,onto the additional exhaust air port (3.1).
For usage in an aggressive environment, we rec
-
ommend using a pneumatic hose to drain all free pneu
-
matic ports in a neutral atmosphere.
Pilot air port
Exhaust air port
Additional exhaust air port
only with servo-assisted
actuating system for high air
flow rate
(actuator size ø 130)
1
3
3.1
Fig.16: Pneumaticconnection
Pilot air hose:
Pilot air hoses of sizes 6/4 mm or ¼" can be used.
Optionally a pilot air port via G⅛" thread is possible.
8.5
Start-up
Perform the
X.TUNE
after installing the device. This function
presets the control parameters.
See control unit operating instructions for a description.
8.6
Disassembly
DANGER!
Risk of injury from discharge of pressure and escaping
medium.
Dismantling a device which is under pressure is hazardous due
to a sudden discharge of pressure or escaping medium.
▶
Before disassembly, shut off the pressure and vent all lines.
Procedure:
→
Loosen pneumatic connection.
→
Disassemble the device.
Type 2301
English
Summary of Contents for 2301 Series
Page 48: ...www burkert com ...