ARC Plus Touch
Never depend on the
remote control for
personal safety.
Always remove power
before performing
maintenance.
MAINTENANCE
MAINTENANCE MODE
should always
be
ON
when working on equipment
that could be remotely activated. In
this mode, remote sites are locked out.
This setting can only be changed for
the local site, so it is important to reset
to
OFF
before leaving the site.
Macros will continue to run while a
unit is in maintenance mode. However, any commands
driven by macros will not be issued. The
If Maint Mode
macro command can be used to test maintenance mode status
(see ARC Plus Version 3 manual for details).
SITE LIMITS
controls the alarm mutes for all channels. You may wish to turn
this
OFF
to suppress alarm reporting during maintenance. This setting can also
be changed remotely.
CONFIGURATION MENU
Press
CONFIG
from the main menu to select the
CONFIGURATION
sub-menu for
the following functions.
METER MUTES
Alarm muting permits testing or abnormal operation
without triggering alarms. From the main menu, press
CONFIG
then
METER MUTES
. Find the desired channel
using the scroll buttons as needed, press the channel then
press
ENABLE
or
MUTE
as appropriate. Meter mutes may
be set on any connected site.
Be sure to restore mutes when normal operation is resumed.
STATUS MUTES
Alarm muting permits testing or abnormal operation
without triggering alarms. From the main menu, press
CONFIG
then
STATUS MUTES
. Find the desired channel
using the scroll buttons as needed, press the channel then
press
ENABLE
or
MUTE
as appropriate. Status mutes may
be set on any connected site.
Be sure to restore mutes when normal operation is resumed.
18