Nivotemp NT MD
open
(0)
closed
(1)
open
(0)
closed
(1)
rising NO contact
falling NC contact
NO (normally open)
rising NC contact
falling NO contact
NC (normally closed)
Hno
Hnc
Note: The designation of the switching function may vary:
Measured variable
5.7.2 Switching output x: Upper switching limit (switching point)
The upper switching limit for switching output Out x can be defined with the following submenu:
Measured variable
____
out_
Measured variable main menu
Out X
____
SPI FHI F I.Hi
Switching point X
____
Selection menu
[ o.Lo - o.Hi ]
Settings menu OUTX
Setting range:
0 °C to 100 °C
(32 °F to 212 °F)
Switching point for OUT x
Note:
– The switching point must be set to within the range limits (see menu
Basic Settings Advanced
Functions
).
– If switching output OUT x was assigned the function
Window
,
will appear. The
setting corresponds with the upper window limit.
– If switching output OUT x was assigned the function
Frequency output
,
will ap-
pear. The setting corresponds to the frequency 100 Hz.
5.7.3 Switching output x: Lower switching limit (switch-back point)
The lower switching limit for switching output Out x can be defined with the following submenu:
Measured variable
____
out_
Measured variable main menu
Out X
____
rPI FLI F I.Lo
Switch-back point X
____
Selection menu
[ o.Lo - o.Hi ]
Settings menu OUTX
Setting range:
0 °C to 100 °C
(32 °F to 212 °F)
Switch-back point for OUT x
Note:
– The switch-back point must be set to within the range limits and must always be lower than the
switching point.
– If switching output OUT x was assigned the function
Window
,
will appear. The
setting corresponds with the lower window limit.
– If switching output OUT x was assigned the function
Frequency output
,
will ap-
pear. The setting corresponds to the frequency 1 Hz.
19
Bühler Technologies GmbH
BE100022 ◦ 11/2020