DHW tank installation
6
9
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Logalux ST400/3, 500/3, 750/3 and 1000/3 "US" • Issue 07/2005
z
Equip and install the DHW pipework in accordance
with state.
6.2
Checking the magnesium anode connection
z
Check that the ground wire (Fig. 6,
Item 1
) for the
magnesium anode (Fig. 6,
Item 2
) is correctly
connected.
6.3
Installing the hot-water temperature sensor (Logamatic or SP34D Control)
If a Buderus Logamatic control or Goldline SP34D
control is used, install the DHW temperature sensor
supplied with the Logamatic or SP34D as follows:
z
Insert the sensor pack including the blank spacers
and wavy compensating spring (Fig. 7,
Item 1
to
4
)
until it bottoms out inside the sensor well (Fig. 7,
Item 5
).
During insertion the plastic spiral (Fig. 7,
Item 3
),
which holds the sensor together, slides back
automatically.
The spring (Fig. 7,
Item 4
) ensures contact between the
sensor well and the sensor surfaces and so a reliable
temperature transfer.
CAUTION!
SYSTEM DAMAGE
through leaking connections.
z
Connect all connection pipes free from
stress.
Fig. 6
Checking the magnesium anode connection
Item 1:
Magnesium anode
Item 2:
Ground wire
1
2
Fig. 7
Installing the DHW temperature sensor package
Item 1:
Blanking piece
Item 2:
Quadrant temperature sensor (or SP34D sensor)
Item 3:
Plastic spiral
Item 4:
Compensating spring
Item 5:
Immersion well (M1)
1
2
4
5
3