DHW tank installation
6
11
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Logalux ST400/3, 500/3, 750/3 and 1000/3 "US" • Issue 07/2005
6.5
Install thermal insulation
The thermal insulating jacket is best installed at
approximately room temperature conditions. Lightly tap
the thermal insulating jackets towards the two ends to
make it easier to pull the ends together.
First attach the sealing strip to the connection lines and
secure with installation aid (U-bar) (Fig. 10,
Item 1
) if
necessary.
z
Place slotted thermal insulating disk on the floor with
the slots near the tank feet (Fig. 10).
z
Place the perforated thermal insulating jackets
around the tank so the holes fit the connections
(Fig. 10).
z
Pull the ends of the thermal insulating jackets
together and close them (Fig. 10).
z
Position thermal insulating disk before front access
port (Fig. 11).
z
Place 4 snap nuts over the holes in the thermal
insulating foil (Fig. 11,
Item 2
).
z
Screw cover over access port with 4 sheet metal
screws (Fig. 11,
Item 1
).
Fig. 10
Position thermal insulating disk and thermal
insulating jackets
Item 1:
Installation aid
1
USER NOTE
The thermal insulating jacket comes in two
parts.
Fig. 11
Attaching thermal insulating disk and thermal
insulating jacket
Item 1:
Sheet metal screw
Item 2:
Snap nut
Item 3:
Thermal insulation disk
Item 4:
Access hand hole cover
Item 5:
Outer tank cover
1
2
5
3
4