LRV lift control valve
Operation
300−I−9010212−E−10/08.08
5.1.4
Description of parameters
5.1.4.1
Demand values Up / Down (1)
Setting "Start speed"
S
Higher value: faster starting speed, shorter starting time, harsher
start−up jolt
S
Setting range:
0.05–0.50V
S
Standard:
0.30V
Important
: low settings for "Start speed" may cause long starting times
Setting "Min. pressure" (UP)
S
Operative during Up travel
S
Higher value: higher solenoid starting voltage, shorter starting time
S
Setting range:
5.0–100.0bar
S
Standard:
20.0bar
Important
: high settings may cause a start−up jerk.
Setting "Offset sol." (DOWN)
S
Operative during Down travel
S
Higher value: higher solenoid starting voltage, shorter starting time
S
Setting range:
1.00–7.00V
S
Standard:
4.00V
Important
: high settings may cause a start−up jerk.
Setting "Acceleration"
S
Higher value: greater acceleration, i.e. shorter acceleration distance
S
Setting range:
0.30–5.00V/s
S
Standard:
2.00V/s