27
26
Thermostat with display
Installer manual
6 Programming
6.4 Temperature calibration detected
By pressing
+
and
–
at the same time it is possible to calibrate the measured temperature. This
function can be disabled using the software.
NOTE:
to reset the factory calibration settings press
+
and
–
(> 7 seconds) at the same time; the
thermometer icon starts flashing quickly.
Keep pressing the keys; after a further 7 seconds the thermometer icon stops flashing, and the
manual calibration is deleted.
The thermometer returns to the factory calibration settings.
Press
+
and
–
at the same time
(> 7 seconds); the thermometer icon
starts flashing quickly. Release the
keys
After releasing the keys, it is possible to increase
or decrease the temperature detected using
+
and
–
.
Wait a few seconds, or press
MODE
or
FAN
to
terminate the procedure.
NOTE:
after the first installation, wait for at least 5 hours before calibrating.