Proceed as follows to inspect and prepare the unit for initial

start-up:

1. Remove all access panels.

2. Read  and  follow  instructions  on  all  WARNING,  CAU

-

TION, and INFORMATION labels attached to, or shipped

with, unit.

3. Make the following inspections:

 a. Inspect  for  shipping  and  handling  damages  such  as

broken lines, loose parts, or disconnected wires, etc.

 b. Inspect  for  oil  at  all  refrigerant  tubing  connections

and on unit base. Detecting oil generally indicates a

refrigerant leak. Leak-test all refrigerant tubing con

-

nections using electronic leak detector, halide torch,

or liquid-soap solution.

 c. Inspect  all  field-wiring  and  factory-wiring  connec

-

tions.  Be  sure  that  connections  are  completed  and

tight. Be sure that wires are not in contact with refrig

-

erant tubing or sharp edges.

 d. Inspect coil fins. If damaged during shipping and han

-

dling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

 a. Make sure that condenser-fan blade are correctly posi

-

tioned in fan orifice. See Condenser Fan Adjustment

section for more details.

 b. Make sure that air filter(s) is in place.

 c. Make  sure  that  condensate  drain  trap  is  filled  with

water to ensure proper drainage.

 d. Make sure that all tools and miscellaneous loose parts

have been removed.

START-UP, GENERAL

Unit Preparation

Make sure that unit has been installed in accordance with in

-

stallation instructions and applicable codes.

In addition to the base unit start-up (unit with electro-mechani

-

cal control), there are a few steps needed to properly start-up

units with optional direct digital controls (DDC). The DDC’s

Service Test function should be used to assist in the base unit

start-up and also allows verification of output operation. Con

-

troller configuration is also part of start-up. This is especially

important when field accessories have been added to the unit.

The  factory  pre-configures  options  installed  at  the  factory.

There may also be additional installation steps or inspection re

-

quired during the start-up process.

Additional Installation/Inspection

Inspect  the  field-installed  accessories  for  proper  installation,

making note of which ones do or do not require configuration

changes. Inspect the DDC Alarms for initial insight to any po

-

tential  issues.  Refer  to  the  Controls,  Start-up,  Operation  and

Troubleshooting Instructions manual for the specific DDC. In

-

spect the SAT sensor for relocation as intended during installa

-

tion. Inspect special wiring as directed below.

Return-Air Filters

Ensure correct filters are installed in unit. (See “APPENDIX B —

PHYSICAL  DATA”  on  page 53.).  Do  not  operate  unit  without

return-air filters.

Outdoor-Air Inlet Screens

Outdoor-air inlet screen must be in place before operating unit.

Compressor Mounting

Compressors are internally spring mounted. Do not loosen or

remove compressor hold down bolts.

Internal Wiring

Check all electrical connections in unit control boxes. Tighten

as required.

Refrigerant Service Ports

Each unit system has two 

1

/

4

-in. SAE flare (with check valves)

service ports: one on the suction line, and one on the compres

-

sor discharge line. Be sure that caps on the ports are tight.

Compressor Rotation

On 3-phase units with scroll compressors, it is important to be cer

-

tain compressor is rotating in the proper direction. To determine

whether or not compressor is rotating in the proper direction:

1. Connect service gages to suction and discharge pressure

fittings.

2. Energize the compressor.

3. The suction pressure should drop and the discharge pres

-

sure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure

does not rise to normal levels:

1. Note that the evaporator fan is  probably also rotating in

the wrong direction.

2. Turn off power to the unit and install lockout tag.

3. Reverse any two of the unit power leads.

4. Re-energize to the compressor. Check pressures.

The suction and discharge pressure levels should now move to

their normal start-up levels.

NOTE: When the compressor is rotating in the wrong direction,

the unit will make an elevated level of noise and will not provide

cooling.

Refrigerant Service Ports

Each system has two 

1

/

4

-in. SAE flare (with check valves) ser

-

vice ports: one on the suction line, and one on the compressor

discharge line. Be sure that caps on the ports are tight.

Cooling

Set space thermostat to OFF position. To start unit, turn on main

power supply. Set system selector switch at COOL position and

fan switch at AUTO. position. Adjust thermostat to a setting be

-

low room temperature. Compressor starts on closure of contactor.

Check  unit  charge.  Refer  to  Refrigerant  Charge  section  on

page 13.

WARNING

ELECTRICAL OPERATION HAZARD

Failure  to  follow  this  warning  could  result  in  personal

injury or death.

The unit must be electrically grounded in accordance with

local codes and NEC ANSI/NFPA 70 (American National

Standards Institute/National Fire Protection Association).

CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution can result in premature wear

and damage to equipment.

Scroll  compressors  can  only  compress  refrigerant  if

rotating  in  the  right  direction.  Reverse  rotation  for

extended  times  can  result  in  internal  damage  to  the

compressor.  Scroll  compressors  are  sealed  units  and

cannot be repaired on site location.

Summary of Contents for Preferred 549K 04-06

Page 1: ...20 Completing Heater Installation 21 SMOKE DETECTORS 21 System 21 Controller 21 Smoke Detector Sensor 22 Smoke Detector Locations 22 Completing Installation of Return Air Smoke Detector 23 FIOP Smoke...

Page 2: ...ON HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintenance operations on unit LOCKOUT TAGOUT the main power switch to unit Electrical sh...

Page 3: ...l need to be periodically replaced or cleaned Filters RETURN AIR FILTERS Return air filters are disposable fiberglass media type Access to the filters is through the small lift out panel located on th...

Page 4: ...he motor s maximum speed Fan speed should be set per job specification CFM cubic feet per minute and ESP external static pressure required and per Fan speed set up label includ ed on the unit s high v...

Page 5: ...els are located on the High Volt age cover in the Control Box 4 Connect a multimeter to the Vdc terminals on the UCB 5 Set the Range Switch to either A B or C per the Switch Range table 6 Using a stra...

Page 6: ...6 8 7 1 7 4 7 7 8 0 8 4 8 7 0 1 0 6 6 9 7 1 7 4 7 7 7 9 8 2 8 5 8 8 0 1 0 8 7 5 7 7 8 0 8 2 8 5 8 7 9 0 0 1 1 0 8 1 8 3 8 5 8 7 9 0 0 1 1 2 8 6 8 8 9 0 9 2 0 1 1 4 9 1 9 3 9 5 0 1 1 6 1 8 2 0 9 6 0 1...

Page 7: ...ny time a motor is replaced the fan rotor is replaced as well The rest of the assembly may be reused See Fig 10 1 Unplug motor harness from control box harness and cut wire tie at the fan deck 2 Unplu...

Page 8: ...e feature on the side of the stator and pull wire harness out through grommet 8 Install rotor on motor by lining up one of 9 holes on com posite rotor with one of 9 holes on motor flange This can be d...

Page 9: ...ved with a vacuum cleaner If a vacuum cleaner is not available a soft non metal lic bristle brush may be used In either case the tool should be applied in the direction of the fins Coil surfaces can b...

Page 10: ...tube sheets to hold the coils apart See Fig 17 Fig 16 Condenser Coil Clips Fig 17 Separating Coil Sections 9 Clean the outer coil surface to remove surface loaded fibers or dirt See Remove Surface Loa...

Page 11: ...tergent in a pressurized spray canister Wash both sides of coil and flush with clean water For best results back flush toward return air section to remove foreign material Flush condensate pan after c...

Page 12: ...hing TXV to distributor 7 Attach the equalizer tube to the suction line If the coil has a mechanical connection then use a wrench and an addi tional wrench on connections to prevent damage If the coil...

Page 13: ...rigerant until the conditions of the appropriate chart are met Note the charging charts are different from type normally used Charts are based on charging the units to the correct sub cooling for the...

Page 14: ...absorbs water readily POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants Avoid exposure of the oil to the atmosphere WARNING FIRE EXPLOSION HAZARD Failure...

Page 15: ...ion discharge pressures are not within specifications for the specific compressor The suction and discharge pressure levels should now move to their normal start up levels Filter Drier Replace wheneve...

Page 16: ...ace thermostat Faulty outdoor fan cooling or indoor fan heating motor or capacitor Replace faulty part Restriction in refrigerant system Locate restriction and remove Defective loader plug Determine c...

Page 17: ...requirements and disconnect switch size and location Route 125 v power supply conductors into the bottom of the utility box containing the duplex receptacle Fig 27 Weatherproof Cover Installation Uni...

Page 18: ...cts be opened to de energize all pow er to the unit Treat all units as electrically energized until the convenience outlet power is also checked and de energization is confirmed Observe National Elect...

Page 19: ...in the space Defrost The defrost control mode is a time temperature sequence There are two time components The continuous run period and the test defrost cycle period The temperature component is prov...

Page 20: ...le point boxes with power distribution and fuse blocks The single point box will be installed directly under the unit control box just to the left of the partition separating the indoor section with e...

Page 21: ...on of supply air and return air Return air smoke detectors are arranged for vertical return configurations only All compo nents necessary for operation are factory provided and mount ed The unit is fa...

Page 22: ...ure between the two tubes pulls the sampled air through the sensing chamber When a sufficient amount of smoke is detected in the sensing chamber the sensor signals an alarm state and the controller au...

Page 23: ...he sampling tube connection is on the bottom and the exhaust tube is on the top 5 Connect the flexible tube on the sampling inlet to the sam pling tube on the basepan 6 For units with an economizer th...

Page 24: ...ty sensor test provides an indication of the sensor s abil ity to compensate for gradual environmental changes A sensor that can no longer compensate for environmental changes is considered 100 dirty...

Page 25: ...tions warrant 1 Disconnect power from the duct detector then remove the sensor s cover See Fig 47 2 Using a vacuum cleaner clean compressed air or a soft bristle brush remove loose dirt and debris fro...

Page 26: ...store it to the normal state RESETTING ALARM AND TROUBLE CONDITION TRIPS Manual reset is required to restore smoke detector systems to Nor mal operation For installations using two sensors the duct sm...

Page 27: ...utomatic at 505 psig 3482 kPa LOW PRESSURE SWITCH The system is protected against a loss of charge and low evapo rator coil loading condition by a low pressure switch located on the suction line near...

Page 28: ...provides the UL required clearance be tween high and low voltage wiring Pass the control wires through the hole provided in the corner post then feed the wires thorough the raceway to the RTU Open Co...

Page 29: ...Economizers use direct drive damper actuators Fig 50 EconoMi er X Component Locations Fig 51 EconoMi er IV Component Locations Fig 52 EconoMi er2 Component Locations IMPORTANT Any economizer that meet...

Page 30: ...r2 is operated by a 4 to 20 mA signal from an existing field supplied control ler See Fig 53 for wiring information 4 3 5 2 8 6 7 1 10 11 9 12 PINK VIOLET BLACK BLUE YELLOW RUN RED WHITE ECONOMI ER2 P...

Page 31: ...r program is available to help with EconoMi er IV training and troubleshooting See Fig 55 and Table 11 for further details Fig 54 EconoMi er IV Functional View LEGEND Fig 55 Typical EconoMi er IV W721...

Page 32: ...mis tor located on the fan deck See Fig 57 This sensor is factory in stalled The operating range of temperature measurement is 0 F to 158 F 18 C to 70 C See Table 12 on page 33 for sensor tem perature...

Page 33: ...per moves to its minimum position The outdoor enthalpy changeover set point is set with the out door enthalpy set point potentiometer on the EconoMi er IV controller The set points are A B C and D See...

Page 34: ...RN DUCT STATIC PRESSURE in wg RELIEF FLOW CFM 3 5 Ton Vertical Economizers Vertical Economizers 0 1000 2000 3000 4000 5000 6000 RETURN AIR FLOW CFM 3 5 Ton HORIZONTAL ECONOMIZER BAROMETRIC RELIEF FLOW...

Page 35: ...ventilation position should be turned fully clockwise Adjust the minimum position potentiometer to allow the mini mum amount of outdoor air as required by local codes to enter the building Make minimu...

Page 36: ...utput of 6 7 volts provides the maximum venti lation rate of 20 or base plus 15 cfm per person Use Fig 63 to determine the maximum setting of the CO2 sensor For ex ample an 1100 ppm set point relates...

Page 37: ...mal after completing troubleshooting DCV MINIMUM AND MAXIMUM POSITION To check the DCV minimum and maximum position 1 Make sure EconoMi er IV preparation procedure has been performed 2 Connect a 9 v b...

Page 38: ...e system The W7220 economizer module pro vides the basic inputs and outputs to provide simple economiz er control When used with the optional sensors the economiz er module provides more advanced econ...

Page 39: ...emperature 40 to 150 F 40 to 65 C Exception of display operation down to 4 F 20 C with full recovery at 4 F 20 C from exposure to 40 F 40 C Storage Temperature 40 to 150 F 40 to 65 C Shipping Temperat...

Page 40: ...ges Menu structure and selection User Interface The user interface consists of a 2 line LCD display and a 4 but ton keypad on the front of the economizer controller Keypad Use the four navigation butt...

Page 41: ...Up Exit button to return to the previous menu Menu Structure Table 17 illustrates the complete hierarchy of menus and pa rameters for the EconoMi er X system The Menus in display order are STATUS SET...

Page 42: ...re Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 to 140 F OUTSIDE AIR TEMP Displays measured value of outdoor air temperature Displays _ _ _F...

Page 43: ...T LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with 1 heat and 2 cool then set...

Page 44: ...f using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode See Menu Note 4 In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump o...

Page 45: ...adjust for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay for...

Page 46: ...A OUTSIDE AIR TEMPERATURE SENSOR ERROR Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A ACTUATOR ERROR Actuator has f...

Page 47: ...nd ary the conditions are not good to economize and the mode is set to NO Figure 70 shows the 5 current boundaries There is also a high limit boundary for differential enthalpy The high limit bound ar...

Page 48: ...3 DLY in Advanced setup COOL Y2 OUT will be turned ON after the delay time specified N A Not applicable STATE FAN SPEED OCC Low Y1 Low Y2 High W High INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV O...

Page 49: ...operational The ex ception is the SAT sensor which will alarm immediately If one or more alarms are present and there has been no keypad ac tivity for at least 5 minutes the Alarms menu displays and...

Page 50: ...ee APPENDIX B PHYSICAL DATA on page 53 Do not operate unit without return air filters Outdoor Air Inlet Screens Outdoor air inlet screen must be in place before operating unit Compressor Mounting Comp...

Page 51: ...etting thermostat at a position below room temperature temporarily shuts unit off until space temperature falls below thermostat setting Ventilation Continuous Fan Set fan and system selector switches...

Page 52: ...E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louvered Hail Guard N Precoat Al Cu Al Cu Louvered Hail Guard P E coat Al Cu Al Cu Louvered Hail Guard Q E coa...

Page 53: ...ct 1 Direct 1 Direct Max Cont BHP 0 71 1 06 1 44 RPM Range 219 2190 217 2170 239 2390 Fan Qty Type 1 Vane Axial 1 Vane Axial 1 Vane Axial Fan Diameter in 16 6 16 6 16 6 High Static 1 Phase Motor Qty D...

Page 54: ...nce tables offer motor drive recommendations In cases when two motor drive combinations would work the lower horsepower option is recommended 6 The EPACT Energy Policy Act of 1992 regulates energy req...

Page 55: ...91 0 95 1050 2079 0 63 2205 0 75 2322 0 87 2430 1 00 1125 2114 0 66 2242 0 78 2359 0 91 2468 1 05 1200 2147 0 69 2277 0 82 2395 0 96 1275 2180 0 72 2310 0 86 2430 1 00 1350 2211 0 75 2343 0 90 2464 1...

Page 56: ...atic 1060 2190 RPM 549K 04N SINGLE PHASE HIGH STATIC 3 TON VERTICAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 900 1060 4 3...

Page 57: ...91 0 95 1050 2079 0 63 2205 0 75 2322 0 87 2430 1 00 1125 2114 0 66 2242 0 78 2359 0 91 2468 1 05 1200 2147 0 69 2277 0 82 2395 0 96 1275 2180 0 72 2310 0 86 2430 1 00 1350 2211 0 75 2343 0 90 2464 1...

Page 58: ...atic 1060 2190 RPM 549K 04N THREE PHASE HIGH STATIC 3 TON VERTICAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 900 1060 4 3...

Page 59: ...1 12 2298 1 29 2400 1 47 1600 1990 0 84 2107 0 99 2219 1 16 2325 1 33 2427 1 52 1700 2024 0 88 2140 1 04 2250 1 20 2354 1 38 2455 1 56 1800 2060 0 92 2174 1 08 2282 1 25 2385 1 43 1900 2097 0 97 2209...

Page 60: ...2170 RPM 549K 05N SINGLE PHASE HIGH STATIC 4 TON VERTICAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 1200 1047 4 3 1251 5 1...

Page 61: ...2400 1 47 1600 1990 0 84 2107 0 99 2219 1 16 2325 1 33 2427 1 52 1700 2024 0 88 2140 1 04 2250 1 20 2354 1 38 2455 1 56 1800 2060 0 92 2174 1 08 2282 1 25 2385 1 43 2484 1 61 1900 2098 0 97 2209 1 13...

Page 62: ...05N THREE PHASE HIGH STATIC 4 TON VERTICAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 1200 1047 3 9 1251 4 7 1431 5 4 1590...

Page 63: ...148 1 04 2256 1 21 2359 1 38 2458 1 56 2553 1 75 2125 2200 1 11 2305 1 28 2407 1 46 2504 1 64 2597 1 83 2250 2254 1 20 2357 1 37 2456 1 55 2551 1 73 2643 1 93 2375 2310 1 28 2410 1 46 2507 1 64 2600 1...

Page 64: ...9 Medium Static 1228 2390 RPM 549K 06N SINGLE PHASE HIGH STATIC 5 TON VERTICAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc...

Page 65: ...256 1 21 2359 1 38 2458 1 56 2553 1 75 2125 2200 1 11 2305 1 28 2407 1 46 2504 1 64 2597 1 83 2250 2254 1 20 2357 1 37 2456 1 55 2551 1 73 2643 1 93 2375 2310 1 28 2410 1 46 2507 1 64 2600 1 83 2690 2...

Page 66: ...m Static 1227 2390 RPM 549K 06N THREE PHASE HIGH STATIC 5 TON VERTICAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 1500 1227...

Page 67: ...89 0 73 2309 0 86 2421 0 99 1125 2088 0 63 2219 0 76 2341 0 89 2454 1 03 1200 2117 0 66 2249 0 79 2372 0 93 2486 1 07 1275 2146 0 69 2278 0 82 2402 0 97 1350 2174 0 72 2307 0 86 2431 1 00 1425 2202 0...

Page 68: ...036 2190 RPM 549K 04N SINGLE PHASE HIGH STATIC 3 TON HORIZONTAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 900 1036 4 2 130...

Page 69: ...89 0 73 2309 0 86 2421 0 99 1125 2088 0 63 2219 0 76 2341 0 89 2454 1 03 1200 2117 0 66 2249 0 79 2372 0 93 2486 1 07 1275 2146 0 69 2278 0 82 2402 0 97 1350 2174 0 72 2307 0 86 2431 1 00 1425 2203 0...

Page 70: ...137 2190 RPM 549K 04N THREE PHASE HIGH STATIC 3 TON HORIZONTAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 900 1037 4 2 1301...

Page 71: ...8 2304 1 26 2409 1 44 1600 1977 0 79 2101 0 95 2218 1 12 2328 1 29 2433 1 47 1700 2005 0 82 2127 0 98 2244 1 15 2353 1 33 2457 1 51 1800 2034 0 86 2155 1 02 2270 1 19 2379 1 37 1900 2066 0 89 2184 1 0...

Page 72: ...1021 2170 RPM 549K 05N SINGLE PHASE HIGH STATIC 4 TON HORIZONTAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 1200 1021 4 2 1...

Page 73: ...09 1 44 1600 1977 0 79 2101 0 95 2218 1 12 2328 1 29 2433 1 47 1700 2005 0 82 2128 0 98 2243 1 15 2353 1 33 2457 1 51 1800 2035 0 86 2156 1 02 2270 1 19 2379 1 37 2482 1 55 1900 2066 0 89 2185 1 06 22...

Page 74: ...549K 05N THREE PHASE HIGH STATIC 4 TON HORIZONTAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vdc 1200 1022 3 8 1228 4 6 1417 5...

Page 75: ...1 12 2336 1 29 2441 1 48 2541 1 66 2125 2157 1 02 2268 1 18 2375 1 36 2478 1 54 2578 1 73 2250 2206 1 08 2313 1 25 2417 1 43 2518 1 61 2616 1 81 2375 2257 1 16 2361 1 33 2461 1 50 2560 1 69 2655 1 89...

Page 76: ...312 9 7 Medium Static 1197 2390 RPM 549K 06N SINGLE PHASE HIGH STATIC 5 TON HORIZONTAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc R...

Page 77: ...2336 1 29 2441 1 48 2541 1 66 2125 2157 1 02 2268 1 18 2375 1 36 2478 1 54 2578 1 73 2250 2206 1 08 2313 1 25 2417 1 43 2518 1 61 2616 1 81 2375 2257 1 16 2361 1 33 2461 1 50 2560 1 69 2655 1 89 2500...

Page 78: ...9 7 Medium Static 1197 2390 RPM 549K 06N THREE PHASE HIGH STATIC 5 TON HORIZONTAL SUPPLY RPM VDC CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 RPM Vdc RPM Vdc RPM Vdc RPM Vdc RPM Vd...

Page 79: ...lectro Mechanical W7220 Controller 208 230 1 60 48TC003160 80 48TC003157 84 208 230 3 60 48TC003156 85 460 575 3 60 48TC003161 81 48TC003158 86 04 06 RTU Open Controller Factory Option 208 230 1 60 48...

Page 80: ...80 APPENDIX D WIRING DIAGRAMS Fig B 549K 04 06 Electro Mechanical Control Wiring Diagram 208 230 3 60 with W7220 Control...

Page 81: ...81 APPENDIX D WIRING DIAGRAMS Fig C 549K 04 06 Electro Mechanical Control Wiring Diagram 460 575 3 60 with W7220 Control...

Page 82: ...82 APPENDIX D WIRING DIAGRAMS Fig D 549K 04 06 208 230 3 60 Units with Optional Factory Installed RTU Open Controller...

Page 83: ...83 APPENDIX D WIRING DIAGRAMS Fig E 549K 04 06 460 575 3 60 Units with Optional Factory Installed RTU Open Controller...

Page 84: ...84 APPENDIX D WIRING DIAGRAMS Fig F 549K 04 06 Power Wiring Diagram 208 230 1 60...

Page 85: ...85 APPENDIX D WIRING DIAGRAMS Fig G 549K 04 06 Power Wiring Diagram 208 230 3 60...

Page 86: ...86 APPENDIX D WIRING DIAGRAMS Fig H 549K 04 06 Power Wiring Diagram 460 575 3 60...

Page 87: ...87 APPENDIX E LOW AMBIENT CONTROL SENSOR LOCATION Fig I 549K 04 Outdoor Circuiting Fig J 549K 05 Outdoor Circuiting SENSOR LOCATION SENSOR LOCATION...

Page 88: ...88 APPENDIX E LOW AMBIENT CONTROL SENSOR LOCATION Fig K 549K 06 Outdoor Circuiting SENSOR LOCATION...

Page 89: ......

Page 90: ...eserves the right to change at any time specifications and designs without notice and without obligations Replaces New 2020 Carrier Cat No 04 53549011 01 Edition Date 12 2020 Printed in U S A Form No...

Page 91: ...vel Y N _____ Verify that fan assembly is free of obstructions and rotor spins freely Y N _____ Verify that scroll compressors are rotating in the correct direction Y N _____ Verify installation of th...

Page 92: ...D LINE Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations CL 2 Replaces New 2020 Carrier Cat No 04 53549011 01 Edition Date 12 2020...

Reviews: