PAGE
SAFETY CONSIDERATIONS
1
. . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION
1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION CONSIDERATIONS
1
. . . . . . . . . . . . . . . . . . .
INSTALLATION
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1 — Thermostat Location
2
. . . . . . . . . . . . . . . . . . . . . . . .
Step 2— Install Thermostat
2
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 3 — Set Thermostat Configuration
2
. . . . . . . . . . . . . . . . .
Step 4 — Thermostat Operation
3
. . . . . . . . . . . . . . . . . . . . . . . .
Step 5 — Check Thermostat Operation
3
. . . . . . . . . . . . . . . . . .
WIRING DIAGRAMS
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency muse use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local
building codes and the current editions of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol
.
When you see this symbol on the unit and in the instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words
DANGER
,
WARNING
, and
CAUTION
. These words are used with the safety--alert symbol.
DANGER
identifies the most serious hazards which
will
result in
severe personal injury or death.
WARNING
signifies a hazard
which
could
result in personal injury or death.
CAUTION
is used
to identify unsafe practices which
may
result in minor personal
injury or product and property damage.
NOTE
is used to highlight
suggestions which
will
result in enhanced installation, reliability, or
operation.
INTRODUCTION
The Legacy Line--RNC Series thermostat is an electronic 24VAC,
non--programmable, manual changeover wall mount thermostat.
This thermostat uses a single setpoint to maintain and control room
temperature in both the heating and air conditioning modes. The
thermostat is designed to ma/-- 2
_
F accuracy. No batteries
are required; temperature, fan, mode, and installer configuration
settings are preserved with power off.
INSTALLATION CONSIDERATIONS
Air Conditioner Model
T1--NAC, Legacy Line--RNC Series Model air conditioner
thermostat, may be wired with or without connecting a common
wire between the indoor equipment and the thermostat. However, it
is recommended to use a common wire whenever possible.
Without a common wire this thermostat becomes “power stealing.”
This means it will need to steal a small amount of power from the
equipment to which it is connected.
NOTE
: Not all HVAC equipment is compatible with power
stealing type thermostats. All Bryant equipment is directly
compatible with this thermostat except the Thermostat Conversion
Kit, Part #TSTATXXCNV10. For all non--Bryant equipment,
consult the system equipment Installation Instructions before
applying this thermostat in a power stealing manner.
Heat Pump Model
T1--NHP, Legacy Line--RNC Series Model heat pump thermostat,
is compatible with all Bryant heat pump systems. It is NOT power
stealing and MUST have both the R and C terminals connected to
operate properly. This thermostat uses a green LED to indicate
auxiliary heat and emergency heat operation.
Summary of Contents for LEGACY LINE-RNC T1-NAC