580J
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNIT
SIZES 04 -- 07 with PURON
r
(R--410A) REFRIGERANT
Submittal Data
Certified to ISO
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
9001
— or —
DESCRIPTION
580J units are single--packaged electric cooling, gas heating
units that are pre--wired and pre--charged with Puron
R
(R--410A) HFC refrigerant. The units are factory tested in
both heating and cooling modes. These units meet the
ASHRAE 90.1--2007 efficiency levels.
STANDARD FEATURES
Base Unit
S
Puron (R--410A) HFC refrigerant
S
SEER’s up to 13.0 (04--06 sizes)
S
EER’s up to 11.0
S
IEER 11.2 (07 size only)
S
Rated in accordance with AHRI Standards 210/240
(04--06 sizes) and 340/360 (07size)
S
Designed in accordance with Underwriters’
Laboratories Std 1995
S
Listed by UL & CUL--Canada or ETL & ETL--Canada
S
Single--stage cooling capacity control
S
Non--corrosive composite sloping design; side or center
drain condensate pan. Meets ASHRAE Standard 62
S
Standard cooling operating range from 40
_
F up to
115
_
F (4
_
C up to 46
_
C). Field installable accessory
extends the minimum down to --20
_
F (--29
_
C)
S
Field convertible from vertical to horizontal airflow for
slab mounting — No special kits required
S
Two--inch disposable return air filters
S
Thru--the--bottom power and gas entry capability
S
Single point gas and electric connections
S
24--volt control circuit protected with resettable circuit
breaker
S
Belt drive, constant torque, permanently lubricated
evaporator--fan motor
S
Totally enclosed condenser motors with permanently
lubricated bearings
S
Low--pressure and high--pressure switches
S
Full perimeter base rail with built--in rigging adapters
and fork truck slots
S
Central Terminal Board facilitating simple safety circuit
troubleshooting and simplified control box arrangement
Cabinet
S
Access panels with easy grip handles
S
Innovative, easy starting, no--strip screw feature on unit
access panels
S
Pre--painted exterior panels and primer--coated interior
panels tested to 500 hours salt spray protection
S
Fully insulated cabinet
S
Tool--less filter access door
Refrigerant System
S
Acutrol
t
refrigerant metering system
S
Liquid line filter drier
S
Scroll compressors with internal line--break overload
protection
S
Copper tube, aluminum fin coils with optional corrosion
resistant coils. Corrosion resistant coils are not available
for single phase (--J voltage) models.
S
Removable gauge line plugs for reading refrigerant
pressure with unit panels in place