Bryant ERVBBSHA1100 Installation Instructions Manual Download Page 1

ERVBBSVA1100, ERVBBSHA1100

HRVBBSVA1100, HRVBBSHA1100

ENERGY/HEAT RECOVERY VENTILATOR

Installation Instructions

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION CONSIDERATIONS

2

. . . . . . . . . . . . . . . . . . .

COMPONENT DESCRIPTION

2

. . . . . . . . . . . . . . . . . . . . . . . .

UNIT INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

WALL CONTROL

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OPERATING THE ERV/HRV WITH
THE EVOLUTION CONTROL

5

. . . . . . . . . . . . . . . . . . . . . . . .

ELECTRICAL CONNECTIONS

6

. . . . . . . . . . . . . . . . . . . . . . . .

ACCESSORIES

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

BALANCING ERV/HRV

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

VENTILATION EVALUATION

8

. . . . . . . . . . . . . . . . . . . . . . . .

CONTROL BOARD OPERATION

8

. . . . . . . . . . . . . . . . . . . . . .

CARE AND MAINTENANCE

8

. . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. Fresh air to building port
2. Exhaust air from building port
3. Fresh air from outside port
4. Exhaust air to outside port

A08103

Fig. 1 -- ERV/HRV Unit (Top Port)

A05330

Fig. 2 -- ERV/HRV Unit (Side Port)

SAFETY CONSIDERATIONS

Installation and servicing of this equipment can be hazardous due
to mechanical and electrical components. Only trained and

qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such

as cleaning and replacing air filters. All other operations must be

performed by trained service personnel. When working on this
equipment, observe precautions in the literature, on tags, and on

labels attached to or shipped with the unit and other safety
precautions that may apply.
Follow all safety codes. Installation must be in compliance with
local and national building codes. Wear safety glasses, protective

clothing, and work gloves. Have fire extinguisher available. Read

these instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.

DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies hazards
which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to highlight

suggestions which

will

result in enhanced installation, reliability, or

operation.

INTRODUCTION

The Energy/Heat Recovery Ventilator (ERV/HRV) is used to

exchange indoor stale air with outside fresh air. The unit is
equipped with a special energy/heat recovery core which transfers

both sensible and/or latent heat between the fresh incoming air and
stale exhaust air. The cross--flow design core allows entering and

leaving air streams to transfer heat and/or latent energy without

mixing (See Fig. 3).

FRESH AIR 

FROM OUTSIDE

STALE AIR 

TO OUTSIDE

STALE AIR 

FROM BUILDING

FRESH AIR 

TO BUILDING

A07460

Fig. 3 -- ERV/HRV Airflow During Air Exchange

(Bottom view with access door removed)

Summary of Contents for ERVBBSHA1100

Page 1: ...be in compliance with local and national building codes Wear safety glasses protective clothing and work gloves Have fire extinguisher available Read these instructions thoroughly and follow all warn...

Page 2: ...ust stale air to outside 7 Electronic control circuit ensures proper unit operation 8 Stale air return from building connected to return air duct system ERV ports on side bottom view 3 2 8 1 4 4 5 6 7...

Page 3: ...airflow through register should not be above 400 ft 122m per minute Maximum length of duct for the system should be designed according to the highest speed of the unit Refer to specifications listed...

Page 4: ...The intake and exhaust hoods should never be located on interior corners or in dead air pockets See Fig 7 Both intake and exhaust hoods must be 18 457mm from ground and at least 12 305mm above antici...

Page 5: ...grated Control All units are equipped with an integrated control located under the unit in front of the electrical compartment Use the push button 1 to control the unit The LED 2 will then shows on wh...

Page 6: ...in personal injury death and or property damage Do not use an extension cord as a power source for operating the ERV HRV WARNING 12VDC Wiring The ERV HRV circuit board wall control and accessories ope...

Page 7: ...e furnace air handler blower OFF If the outside temperature is below 32_F 0_C make sure the unit is not running in defrost while balancing By waiting 10 minutes after plugging the unit in you are assu...

Page 8: ...pens contact on K5 relay which opens outside air damper Then 115VAC is applied between orange and gray wires on Molex plug pins 1 and 6 and blower motor runs in high speed operation Low Speed Air Exch...

Page 9: ...st cycle every 20 minutes This feature is not there on older board versions with 3 pin jumpers Override Test To use override test function a thermistor must be connected to the control board Unit must...

Page 10: ...dehumidistat does not work OR the 20 minute push button timer does not work OR its indicator light does not stay on S The wires may be in reverse position S Ensure that the color coded wires have bee...

Page 11: ...2 16560 55 13 15900 57 14 15280 59 15 14690 61 16 14120 63 17 13580 64 18 13060 66 19 12560 68 20 12090 70 21 11630 72 22 11200 73 23 10780 75 24 10380 77 25 10000 79 26 9632 81 27 9281 82 28 8944 84...

Page 12: ...AMPER ELECTRONIC ASSEMBLY Defrost temperature sensor S1 ICP CONNECTION DIAGRAM Line voltage factory wiring Class 2 low voltage factory wiring Class 2 low voltage field wiring COLOR CODE B LK BLACK B L...

Page 13: ...tch J11 2 J11 1 K1 K3 K5 J14 3 J14 1 J14 2 AIR HANDLER FAN INTERLOCK 24VAC CLASS 2 CIRCUIT ONLY optional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10 Override optional see notes 3 4 Field...