background image

4

PISTON BODY

LIQUID SERVICE VALVE

PISTON

PLASTIC WASHER

ADAPTER TUBE

BRASS NUT

A14235

Fig. 4 -- Liquid Service Valve with Heating Piston and

Adapter Tube

Brazing Connections

FIRE HAZARD

Failure to following this warning could result in personal

injury, death and/or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes

and contacts brazing torch. Make sure the refrigerant charge is

properly removed from both the high and low sides of the

system before brazing any component or lines.

!

WARNING

Connect vapor tube to fitting on outdoor unit vapor service valves

(see Table 2). Connect liquid tubing to adapter tube on liquid

service valve. Use refrigerant grade tubing.

Table 2 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

UNIT SIZE

LIQUID

RATED VAPOR*

Connection

Diameter

Tube

Diameter

Connection

Diameter

Tube

Diameter

024

3/8

3/8

3/4

3/4

036

3/8

3/8

7/8

7/8

048, 060

3/8

3/8

7/8

1--1/8

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance

data when using different size and length linesets.

Notes

:

1. Do not apply capillary tube indoor coils to these units.

2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or

20 ft. (6.1 m) vertical differential, refer to the Residential Piping and Longline

Guideline.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat–sinking material

such as a wet cloth while brazing.

Apply heat absorbing paste or heat sink product between service

valve and joint. Wrap service valves with a heat sinking material
such as a wet cloth.
After wrapping service valve with a wet cloth, tubing set can be

brazed to service valve using either silver bearing or non–silver

bearing brazing material. Do not use soft solder (materials which

melt below 800

°

F/427

°

C). Consult local code requirements.

NOTE

: Some outdoor units contain a mechanical fitting at the

liquid distributor. This connection is not field serviceable and

should not be disturbed.

NOTE

: For Liquid Service Valve -- Braze lineset to adapter tube

BEFORE bolting adapter to valve. This helps prevent overheating
and damage to plastic washer or o--ring.

For Vapor Service Valve -- remove valve core from schrader port
on Service Valve BEFORE brazing.

This helps prevent

overheating and damage to valve seals (refer to Fig. 5). Replace
valve core when brazing is completed.

VALVE CORE

SERVICE VALVE

A14236

Fig. 5 -- Vapor Service Valve

Clean line set tube ends with emery cloth or steel brush. Remove
any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between service

valve and joint. Wrap service valves with a heat sinking material

such as a wet cloth.
Braze joints using a Sil--Fos or Phos--copper alloy.

Install Liquid Line Filter Drier Indoor

Refer to Fig. 6 and install filter drier as follows:

1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from

step 1.

4. Connect and braze liquid refrigerant tube to the filter drier.

A05227

Fig. 6 -- Liquid Line Filter Drier

Refrigerant tubing and indoor coil are now ready for leak testing.

This check should include all field and factory joints.

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the

recommended deep vacuum method of 500 microns. The alternate

triple evacuation method may be used (see triple evacuation
procedure in service manual). Always break a vacuum with dry

nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of

accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and

Summary of Contents for BH17NA

Page 1: ...a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing...

Page 2: ...including adverse weather conditions Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service...

Page 3: ...ried without further special consideration Do not bury lines longer than 36 in 914 4 mm Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant gr...

Page 4: ...OTE Some outdoor units contain a mechanical fitting at the liquid distributor This connection is not field serviceable and should not be disturbed NOTE For Liquid Service Valve Braze lineset to adapte...

Page 5: ...ssible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit...

Page 6: ...nfigurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire from cool tap is connec ted to tap 5 on the motor Refer to the furnace Product Data to find...

Page 7: ...ssor has been off for 5 minutes or power has not been cycled for 5 minutes the OF2 relay and T2 terminal will energize This will close the contactor and start the outdoor fan motor and compressor When...

Page 8: ...s between 70_F and 100_F 21 11_C and 37 78_C and the indoor temperature is between 70_F and 80_F 21 11_C and 26 67_C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjus...

Page 9: ...and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fill...

Page 10: ...Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wr...

Reviews: