background image

NOTE:

Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.

WARNING:

Before installing, modifying, or servicing

system, main electrical disconnect switch must be in the
OFF position. There may be more than 1 disconnect
switch. Lock out and tag switch(es) with a suitable
warning label. Electrical shock can cause personal injury
or death.

INSTALLATION RECOMMENDATIONS

NOTE:

In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where

unit operation sounds may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate

to capacity of unit.

3. Run refrigerant tubes as directly as possible by avoiding

unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb

vibration.

5. When passing refrigerant tubes through the wall, seal

opening with RTV or other pliable silicon-based caulk. (See
Fig. 3.)

6. Avoid direct tubing contact with water pipes, duct work,

floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with

a rigid wire or strap which comes in direct contact with
tubing. (See Fig. 3.)

8. Ensure that tubing insulation is pliable and completely

surrounds vapor tube.

9. When necessary, use hanger straps which are 1 in. wide and

conform to shape of tubing insulation. (See Fig. 3.)

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

Fig. 1—Models 661C

A94355

Fig. 2—Models 661G and 661S

A98524

installation and
start-up instructions

10 SEER
SPLIT-SYSTEM
HEAT PUMP

Cancels:

II 661C-18-6

II 661C-18-7

2-02

661C, G

661S

—1—

Summary of Contents for 661C

Page 1: ...t and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING Before installing modifying or servicing system main electrical...

Page 2: ...e for wind baffle construction NOTE Unit must be level to within 2 3 8 in ft per compressor manufacturer specifications III CLEARANCE REQUIREMENTS When installing allow sufficient space for airflow cl...

Page 3: ...onnected to Factory Approved In door Unit Outdoor unit contains correct system refrigerant charge for opera tion with indoor unit of same size when connected by 15 ft of field supplied or factory acce...

Page 4: ...measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace trans...

Page 5: ...wires from crimp nut in indoor fan coil when installing outdoor thermostats IMPORTANT When using outdoor thermostats W2 must be energized when requesting supplemental heat EHR EHR EHR 24 VAC HOT R G...

Page 6: ...an coil when installing outdoor thermostats IMPORTANT When using outdoor thermostats W2 must be energized when requesting supplemental heat EHR EHR EHR IF AVAILABLE 24 VAC HOT R C W2 Y G R W3 W2 E G R...

Page 7: ...E If the phasing is incorrect the contactor will not be energized To correct the phasing interchange any two of the three power connections on the field side When thermostat is satisfied its contacts...

Page 8: ...it This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units If pressure and temperature do not match on chart...

Reviews: