Brugg Pipesystems GERMANPIPE LMS 120 Operating And Service Instructions Download Page 1

Brugg LMS 120 monitoring device 

Operating and service instructions 

Art.-Nr.: 

1010368

Summary of Contents for GERMANPIPE LMS 120

Page 1: ...Brugg LMS 120 monitoring device Operating and service instructions Art Nr 1010368...

Page 2: ...onnection 6 4 Operation 7 4 1 Display and operating elements 7 4 2 Operation menu 8 4 3 Quick parameter setting 9 4 4 Enhanced parameter setting 10 4 5 Alarm menu 13 4 6 Manual measurement 14 4 7 Firm...

Page 3: ...Incorrect wiring of the connections may result in faults or defective devices The manufacturer accepts no liability for accidents that are caused by incorrectly installed or improperly maintained devi...

Page 4: ...different system types at the same time As such it is possible to connect one line with the NORDIC system on measurement channel 1 and one line with the BRANDES system on measurement channel 2 for ins...

Page 5: ...ernatively in a control cabinet At the place of installation the device must be protected against humidity formation of condensation strong dust and strong electromagnetic fields The safety notes prot...

Page 6: ...30V Fig 4 Wiring diagram 3 2 2 Earth connection To ensure smooth operation the earth contact pipe of every measurement circuit must be connected with the associated pipeline When replacing existing l...

Page 7: ...rameter setting menus are shown by the info display 4 1 Display and operating elements Description Symbol Description Cursor keys Left right in the menu Up down in the menu Confirmation OK Alarm menu...

Page 8: ...nnel 1 2 Status OK Alarm Loop Alarm Iso Alarm I L Operation display 2 The values of the last measurement are displayed here Explanation I Isolation value measure of dampness of thermal isolation L Loo...

Page 9: ...After activating the service menu see 4 3 1 perform the following steps Procedure 1 System Defaults 11 is displayed 2 Select NORDIC BRANDES or SWISS 3 Confirm selection Setting channel defaults is di...

Page 10: ...n 4 3 Quick parameter setting on page 9 are not suitable or when the limits should be or have to be modified This multi step menu is arranged on two levels where the desired settings can be made with...

Page 11: ...ossible settings NORDIC SWISS BRANDES 10 k 20 M Loop alarm menu 23 33 The limit for triggering an alarm can be set with the keys If the measurement for the loop resistance exceeds the limit the LMS 12...

Page 12: ...saved see 4 5 Alarm menu page 13 Example Measure cycle 6 h Error number 092 Fault since 92 x 6 h 552 h 23 days Possible settings 2min 30min 1h 24h Buzzer menu 42 The LMS 120 issues an acoustic signal...

Page 13: ...us and the number of faults of the isolation resistance are shown in this display Possible displays are No Alarms Active Alarms Old Alarms Alarm menu 05 is used to clear the alarm log and to set all c...

Page 14: ...the manual measurement hold down for 5 sec The measurement starts as soon as the LED starts to flash At the end of the process the LED goes out and operation menu 1 is displayed 4 7 Firmware update Ne...

Page 15: ...should be used for a service report 6 Service In the operation menu display 3 provides coded information on the setting and measurement values of the LMS 120 see 4 2 Operation menu page 8 It offers th...

Page 16: ...report can also be sent online at www visileak com Customer Company Name Address Country Telephone Building property Name Address Note Error Description Error since Measured values Loop 1 Type Nordic...

Page 17: ...stallation screws Materials and colour Housing Polystyrene grey similar to RAL 7035 Lid Polycarbonate transparent Protection category IP 65 in accordance with EN 60529 Weight excl packaging 1 1 kg Mea...

Page 18: ...arm Schleifenfehler On On Alarm I L Alarm Isolations und Schleifenfehler Pass durchgef hrt Auto Automatisch Pipe Rohr Back zur ck Power Netzspannung Buzzer Signalhupe Save sichern Channel Kanal Self T...

Page 19: ...Operating and service instructions LMS 120 19 10 Notes...

Page 20: ...x 41 56 268 78 79 www pipesystems com BRUGG Rohrsysteme GmbH Adolf Oesterheld Stra e 31 D 31515 Wunstorf phone 49 5031 170 0 fax 49 5031 170 170 www brugg de GERMAN PIPE Industrie und Fernw rmetechnik...