7. Commissioning
7.1 Configuration
The setting level will be called up by holding down the presence key. Parameters
are selected by pressing the presence key briefly. The selected parameter flashes.
Select the required value with the rotary selector. Programming is terminated by
pressing the operating mode key.
Tab. 2: Parameters
Function
Setting
Use as
ru = 1 (factory settings)
The room controller is addressed as room controller 1 (for
heating circuit 1).
ru = 2 (factory setting)
The room controller is addressed as room controller 2 (for
heating circuit 2).
ru = 3
The room controller is addressed as room controller 3 (for
heating circuit 3).
Direct adjustment (set
room temperature)
P1 = 1 (factory settings)
The setting is saved automatically: A set temperature cor-
rection can either be confirmed by pressing the operating
mode key, or without any further confirmation (timeout)
(factory settings).
P1 = 2
The setting is saved after confirmation: A set temperature
correction is only saved after having been confirmed by
pressing the operating mode key.
Operation block
P2 = 0
OFF: All controls are enabled (factory setting).
P2 = 1
OFF: The following controls are blocked:
- Operating mode changeover, heating circuit
- Set comfort temperature adjustment
- Operating level changeover (presence key)
With active operation block, the display shows "OFF" for ap-
prox. 3 s after pressing a key. The operation block will not
prevent the setting level from being called up.
For detailed information on programming the ISR integrated system controller and
setting tables with the programmable parameters, see the
installation manual
of
the boiler.