4. Commissioning
4.1 Presetting
The control units in gas condensing boilers of the Paramount three/four 60-115
series are preset not to actuate a modulating pump.
4.2 Use as heating circuit pump
Settings if used as a heating circuit pump
If the pump HEP is used as a heating circuit pump, under prog. no. 6085, make the
setting shown in the following table.
Function
Prog. no.
Setting level
Setting
Configuration
PWM output P1
6085
E
Heating circuit pump HC1 Q2
or
Heating circuit pump HC2 Q6
or
Heating circuit pump HC3
Q20
1) Alternative setting if heating circuit 2 is to be supplied
2) Alternative setting if heating circuit 3 is to be supplied
Set the minimum and maximum pump speeds in accordance with the system con-
figuration under menu item
Heating circuit 1-heating circuit 3
Function
Prog. no.
Setting level
Setting
Heating circuit 1
Pump speed min
882
E
Pump speed max
883
E
Heating circuit 2
Pump speed min
1182
E
Pump speed max
1183
E
Heating circuit 3
Pump speed min
1482
E
Pump speed max
1483
E
Commissioning
7660118-03
07.16
Variable speed pump HEP 25-180-10
27
GB