1-10
Section 1 - Introduction
Installation and Operation Manual
X-TMF-SLAMf-MFC-eng
Part Number: 541B032AAG
August, 2009
Brooks
®
Digital MFC's and MFM's
F
OUNDATION
®
Fieldbus Communications:
The Brooks SLAMf Digital Series is supporting F
OUNDATION
®
Fieldbus
communication protocol. F
OUNDATION
®
Fieldbus is a digital network allowing
usage of existing 4-20mA cables, avoiding costly re-wiring. Fully certified
by passing ITK, this device has passed several Interoperability
requirements over a broad range of hosts. When combined with DeltaV
and using the power of PlantWeb, those devices provide intelligent alerts
allowing accurate device maintenance and service.
•
Value Range check - Part of the standard function blocks
•
Temperature sensor connection - Check sensor connection
•
Firmware checksum - Check for Internal firmware integrity
•
Non-volatile memory - Check for non-volatile memory integrity
•
RAM - Check for RAM integrity
•
Zero Drift/Valve Leak-by - Check for flow leak-by or sensor zero drift
•
Device Overhaul due - Preventive Maintenance
•
Calibration Due - Preventive Maintenance
•
Valve spring life - Preventive Maintenance
•
No Flow - No flow detected when setpoint requested
•
Reverse Flow - Reverse flow detected
•
Flow Totalizer - Informed when a user define amount of fluid has been
delivered
•
Time Totalizer - Informed when a user define amount of time has
expired
Device type dependant function block are available representing the
different device functions:
•
Current Flow Value (Mass Flow device only)
•
Current Pressure Value (Pressure device only)
•
Current Device Temperature (Mass Flow device only)
•
Current Valve position (Controller Only)
•
Setpoint Control (Controller Only)
•
Direct Valve Control (Controller Only)
•
Actuator Override (Controller Only)
•
Ultra-fast (8ms) PID function block for Cascade control
(all devices)