![Brooks Firetracker FT420 Technical Manual Download Page 10](http://html1.mh-extra.com/html/brooks/firetracker-ft420/firetracker-ft420_technical-manual_2818733010.webp)
Technical Manual
FT420
– Iss 2.4
10
1.4 Specifications
Table 1 General Specifications
Feature
Specification
Mains Power Supply
230V
AC
(86-265V
AC
), 150W (5.5 Amp), requirement is based on the CIE power
supply calculations, refer to Chapter 3.12 page 54.
Backup Battery
2 x 12V. Battery capacity is based on the CIE power supply calculations. Refer to
Chapter
“Power Supply Calculations” page 55
Access Security
Access Level 1: All the LED indicators are viewable through the locked transparent
front door.
Access Level 2: All the controls are accessible by opening the front transparent door
using a 003 key.
Access Level 3: The control and indicating circuits are behind the front plate. To
repair the CIE or upgrade its firmware, the technician needs to open the outer door
and unscrew the inner door.
Access Level 4: All the system configurations require special hardware and PC
software. No configuration is available during normal operations (Access Level 1 &
2).
Operating Temperature
0°C to +40°C.
Operating Humidity
5-95%, non-condensing.
IP Rating
IP31
Enclosue Material
Zinc anneal steel powder coated oyster with a tinted lockable acrylic front door
Enclosure
Small
480 (High) X 450 (Wide) X 220 (Deep) mm
Medium
630 (High) X 450 (Wide) X 220 (Deep) mm
Large
920 (High) X 450 (Wide) X 220 (Deep) mm
Compliance
CIE:
Conforms to AS7240.2-2004 and AS7240.4-2004
OWS:
Meet the requirements of clause 3.22 of AS1670.1-2004 and clause 1.4.1,
1.4.4, 4.3.3 and 4.3.5 of AS1670.4-2004
Alert tone and message meet the requirements of ISO 7731
Evacuation tone and message meet the requirements of ISO 8201
Gaseous extinguishing system meets the requirements of AS4214
Applications
Normally used in Class 2, 3, 4, 5 & 6 buildings, can also be used to protect
hazardous locations using intrinsically safe detectors/ MCP
’s via galvanic isolator.
Installed to in-door environment only. Upon request it can be fitted inside IP65
enclosure.