Brooks Instrument Model 5866 Pressure Controller
5-14
Since the C
v
calculated is the same as listed for the .014" orifice the .020"
orifice should be selected. The last step is to check the maximum pressure
drop for the application. The maximum pressure drop for the .020 orifice is
300 psi, this is greater than the 100 psi pressure drop required for the
application so the .020" orifice is correct.
Table 5-4. Model 5866 Orifice Selection.
Orifice
Maximum
C
v
Size
Pressure Drop (psi)
5.0x10
-6
.001
1500
2.0x10
-5
.002
1500
5.0x10
-5
.003
1500
1.1x10
-4
.004
1500
4.0.x10
-4
.007
1500
9.0x10
-4
.010
750
2.0x10
-3
.014
550
4.7x10
-3
.020
300
1.4x10
-2
.032
175
3.5x10
-2
.048
85
5.5x10
-2
.062
55
8.0x10
-2
.078
50
1.0x10
-1
.093
50
1.4x10
-1
.116
50
1.5x10
-1
.120
50
Figure 5-6. Example Application of Orifice Sizing Procedure.
®
Reactor
N
2
Model 5850E
Mass Flow Controller
500 sccm, Full Scale
®
Model 5866
Vent to
Atmosphere
H
2
Model 5850E
Mass Flow Controller
300 sccm, Full Scale
®
100 psig
Maximum
Desired
Pressure
Summary of Contents for 5866
Page 20: ...3 3 Operation Figure 3 2 Proportional Control Figure 3 3 Integral Control ...
Page 21: ...Brooks Instrument Model 5866 Pressure Controller 3 4 Figure 3 4 P I Control ...
Page 23: ...Brooks Instrument Model 5866 Pressure Controller 4 2 ...
Page 32: ...5 9 Troubleshooting Figure 5 3 Valve Adjusting Spacer Locations ...
Page 34: ...5 11 Troubleshooting Figure 5 4 Valve Adjusting Spacer Locations Normally Open N O Valve ...
Page 43: ...Brooks Instrument Model 5866 Pressure Controller 6 6 ...
Page 45: ...Brooks Instrument Model 5866 Pressure Controller 7 2 Figure 7 1 Model 5866E Parts Drawing ...
Page 47: ...Brooks Instrument Model 5866 Pressure Controller 7 4 Figure 7 2 Model 5866M Parts Drawing ...
Page 48: ...7 5 Parts List Table 7 3 Model 5866M Parts List ...
Page 49: ...Brooks Instrument Model 5866 Pressure Controller 7 6 ...
Page 65: ......