TABLE 5 NEBS thermal policy levels (continued)
Level
Description
Temperature
RPM
2
MED-LOW
from 25C through 35C
4000 RPM
3
MED
from 36C through 45C
5500 RPM
4
HIGH
from 46C through 55C
7350 RPM
5
MAX
from 56C through 61C
9300 RPM
CAUTION
For the NEBS-compliant installation of a Brocade device with AC or DC systems, use a ground wire of at least 2 AWG. The
ground wire should have an agency-approved crimped connector (provided with the device) attached to one end, with the other
end attached to building ground. The connector must be crimped with the proper tool, allowing it to be connected to both
ground screws on the enclosure. Before crimping the ground wire into the provided ground lug, ensure that the bare copper
wire has been cleaned and antioxidant is applied to the bare wire. In addition, anti-rotation devices or lock washers must be
used with all screw connections for the grounding wire.
Time and items required for the installation
You can set up and install the Brocade device in the following ways:
∙
As a standalone unit on a flat surface
∙
In a 19-inch Electronic Industries Association (EIA) rack, using the four-post rack mount kit
∙
In a two-post telecommunications (Telco) rack
The following table describes the installation tasks, the estimated time required for each, and the items required to complete the task
based on a fully populated chassis (384 10 GbE ports). Configurations with fewer ports require less time. These time estimates assume a
prepared installation site and appropriate power and network connectivity.
DANGER
The procedures in this manual are for qualified service personnel.
TABLE 6 Installation tasks, time, and items required
Installation task
Time estimate
Items required
Site preparation and unpacking the device
30 minutes
#2 Phillips screwdriver
Pallet jack.
Hydraulic lift or assisted lift, able to raise to a
minimum of 140 cm (55 in.), with a minimum
capacity of 113 kg (250 lb).
To know the weight of your device fully
populated with the required port blades, refer to
the Technical Specifications at the end of this
guide.
Installing rack mount kit
30 minutes
Refer to the rack mount kit instructions for the
device.
Mounting and securing the device in rack
30 minutes
Installing power cables and powering on the
device
20 minutes
Power cables (provided in the device
accessories kit).
Establishing serial connection, logging on to the
device, and configuring the IP addresses.
20 minutes
Serial cable (provided in the accessory kit).
Workstation computer with a serial (console) port
or terminal server port and a terminal emulator
application (such as HyperTerminal).
Preparing for Installation
Brocade VDX 8770-4 Hardware Installation Guide
30
53-1002563-10
Summary of Contents for VDX 8770-4
Page 8: ...Brocade VDX 8770 4 Hardware Installation Guide 8 53 1002563 10...
Page 12: ...Preface Brocade VDX 8770 4 Hardware Installation Guide 12 53 1002563 10...
Page 14: ...About This Document Brocade VDX 8770 4 Hardware Installation Guide 14 53 1002563 10...
Page 26: ...Product Overview Brocade VDX 8770 4 Hardware Installation Guide 26 53 1002563 10...
Page 70: ...Mounting the Device Brocade VDX 8770 4 Hardware Installation Guide 70 53 1002563 10...