4. Remove the serial cable from the active CP blade and attach it to the standby CP blade.
5. Type
firmwareDownload -s -U v
X.X.X
(where
X.X.X
is the firmware version you are downloading) to download the firmware to
the standby CP blade.
The
-s
option also disables the autoreboot, so you must manually issue a reboot after the download finishes to initiate
firmwarecommit. Enter all requested information (use default values).
The
-U
option indicates that the download should come from the USB device. If you do not use this option, you are prompted
with
Download from USB [No}:
Type
Y
to download from the USB device.
6. When the download process finishes, type
firmwareDownloadStatus
to verify that the firmware has been updated.
7. Ensure that you are still logged in to the standby CP blade (the blade for which you just changed the firmware level) and type
reboot
. The reboot of the standby CP will initiate a firmwarecommit to the secondary partition and log you out.
8. Log back in to the standby CP blade and type
firmwareDownloadStatus
on the standby CP blade to validate a successful
commit. This may take 10 minutes.
9. Log out of the standby CP blade and log in to the active CP blade.
10. Type
haEnable
to re-enable HA on the active CP blade.
11. Type
haShow
and verify that the command output includes "HA enabled, Heartbeat Up, HA State synchronized". If not, re-enter
the command until you have verified that redundancy is achieved.
12. Type
firmwareShow
to verify that the firmware version has been updated and that the versions are the same on the two CP
blades.
13. Pack the faulty CP blade in the packaging provided with the new CP blade, and contact the switch supplier to determine the
return procedure.
14. Replace the chassis door (
Removal and replacement of the chassis door
on page 83).
Removal and replacement of the core switch blade
(CR8)
This section describes how to remove and replace a core switch blade (CR8). The Brocade DCX has two core switch blades: one in slot 5
and one in slot 8. Note that the blade shown in the removal illustration (
Removing a core switch blade (CR8)
on page 98) is shown with
EMI plugs installed.
Time and items required
The replacement procedure for the core switch blade takes approximately 30 minutes. The following items are required for the core
switch blade replacement:
•
ESD grounding strap
•
#2 Phillips screwdriver
•
Replacement Brocade DCX CR8 core switch blade
Verifying the necessity of replacement
Confirm that you need to replace the core switch blade. The following events might indicate that a core switch blade is faulty:
•
The status LED on the core switch blade is lit amber, or the power LED is not lit.
•
The
slotShow
command does not show that the core switch blade is enabled.
Removal and replacement of the core switch blade (CR8)
Brocade DCX Backbone Hardware Installation Guide
53-1000685-24
97
Summary of Contents for DCX Backbone
Page 8: ...Brocade DCX Backbone Hardware Installation Guide 8 53 1000685 24...
Page 12: ...Brocade DCX Backbone Hardware Installation Guide 12 53 1000685 24...
Page 14: ...Brocade DCX Backbone Hardware Installation Guide 14 53 1000685 24...
Page 24: ...Brocade DCX Backbone Hardware Installation Guide 24 53 1000685 24...
Page 28: ...Brocade DCX Backbone Hardware Installation Guide 28 53 1000685 24...
Page 46: ...Brocade DCX Backbone Hardware Installation Guide 46 53 1000685 24...
Page 50: ...Brocade DCX Backbone Hardware Installation Guide 50 53 1000685 24...
Page 82: ...Brocade DCX Backbone Hardware Installation Guide 82 53 1000685 24...
Page 138: ...Brocade DCX Backbone Hardware Installation Guide 138 53 1000685 24...
Page 142: ...Brocade DCX Backbone Hardware Installation Guide 142 53 1000685 24...
Page 148: ...Brocade DCX Backbone Hardware Installation Guide 148 53 1000685 24...