5500 Watt  Portable  Generator

8

USING THE  GENERATOR

System Ground

The generator has a system ground that connects the
generator frame components to the ground terminals on
the AC output receptacles.The system ground is connected
to the AC neutral wire (the neutral is bonded to the
generator frame).

Special Requirements

There may be Federal or State Occupational Safety and
Health Administration (OSHA) regulations, local codes, or
ordinances that apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or
the local agency having jurisdiction.

• In some areas, generators are required to be registered

with local utility companies.

• If the generator is used at a construction site, there may

be additional regulations which must be observed.

Connecting to a Building’s Electrical

System

Connections for standby power to a building’s electrical
system must be made by a qualified electrician.The
connection must isolate the generator power from utility
power, and must comply with all applicable laws and
electrical codes.

Generator Location

Generator Clearance

The generator must be at least 5 ft. (152 cm) from
structures having combustible walls and/or other
combustible materials. Leave at least 3 ft. (92 cm) all around
generator including overhead, for adequate cooling,
maintenance and servicing.

Place generator in a well ventilated area, which will allow
for removal of deadly exhaust gas. DO NOT place
generator where exhaust gas could accumulate and enter
inside or be drawn into a potentially occupied building.
Ensure exhaust gas is kept away from any windows, doors,
ventilation intakes or other openings that can allow exhaust
gas to collect in a confined area (Figure 3). Prevailing winds
and air currents should be taken into consideration when
positioning generator.

• When using generator for backup power, notify utility

company. Use approved transfer equipment to isolate
generator from electric utility.

• Use a ground fault circuit interrupter (GFCI) in any damp or

highly conductive area, such as metal decking or steel work.

• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are worn,

frayed, bare or otherwise damaged.

• DO NOT operate generator in the rain.
• DO NOT handle generator or electrical cords while standing

in water, while barefoot, or while hands or feet are wet.

• DO NOT allow unqualified persons or children to operate or

service generator.

Generator produces powerful voltage.
Failure to isolate generator from power utility
can result in death or injury to electric utility
workers due to backfeed of electrical energy.

WARNING

• Operate generator ONLY outdoors.
• Install a battery operated carbon monoxide alarm near the

bedrooms.

• Keep exhaust gas from entering a confined area through windows,

doors, ventilation intakes or other openings.

• DO NOT operate generator inside any building or enclosure,

including the generator compartment of a recreational vehicle (RV).

Running generator gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea,
fainting or death.

WARNING

Figure 3 — Generator Clearance

Exhaust Port

Typical Generator Shown

Summary of Contents for Elite 030206

Page 1: ...pas besoin d aller loin pour trouver de l aide Preguntas La ayuda es justa un momento lejos Call Generator Helpline Appelez Ligne d assistance de G n rateur Llame L nea Directa del Generador 1 800 74...

Page 2: ...wner s manual SAFETY RULES This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or dea...

Page 3: ...r openings DO NOT operate generator inside any building or enclosure including the generator compartment of a recreational vehicle RV Running generator gives off carbon monoxide an odorless colorless...

Page 4: ...STING OR MAKING REPAIRS TOYOUR GENERATOR Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug WHEN TESTING FOR ENGINE SPARK Use approved spark plug...

Page 5: ...ris out of intake air Choke Lever Used when starting a cold engine Data Tag Provides model revision and serial number of generator Please have these readily available when calling for assistance Fuel...

Page 6: ...is not intended for over the road use You will need a socket wrench with 1 2 or 13mm sockets and a needle nose pliers to install this kit Install the Wheel Kit as Follows 1 Place the bottom of the ge...

Page 7: ...l lubrication for the life of the bearing Add Fuel NOTE This gasoline engine is certified to operate on gasoline Exhaust Emission Control System EM Engine Modifications 1 Use clean fresh regular UNLEA...

Page 8: ...mulate and enter inside or be drawn into a potentially occupied building Ensure exhaust gas is kept away from any windows doors ventilation intakes or other openings that can allow exhaust gas to coll...

Page 9: ...n engine off according to instructions given in the engine owner s manual 4 Move fuel valve to Off position See Don t Overload Generator Start generator and let engine stabilize before connecting elec...

Page 10: ...20 Amp Duplex Receptacles The duplex receptacle Figure 6 is protected against overload by a rocker switch circuit breaker Use each receptacle to operate 120 Volt AC single phase 60 Hz electrical loads...

Page 11: ...tor output to stabilize engine runs smoothly and attached device operates properly 4 Plug in and turn on the next load 5 Again permit the generator to stabilize 6 Repeat steps 4 and 5 for each additio...

Page 12: ...DO NOT use a garden hose to clean generator Water can enter engine fuel system and cause problems In addition if water enters generator through cooling air slots some of the water will be retained in...

Page 13: ...from forming in fuel system or on essential carburetor parts add fuel stabilizer into fuel tank and fill with fresh fuel Run the unit for several minutes to circulate the additive through the carburet...

Page 14: ...t no load but bogs down when loads are connected 1 Short circuit in a connected load 2 Generator is overloaded 3 Shorted generator circuit 1 Disconnect shorted electrical load 2 See Don t Overload Gen...

Page 15: ...d apologize to you for being inconvenienced Any Authorized Service Dealer may perform warranty repairs Most warranty repairs are handled routinely but sometimes requests for warranty service may not b...

Page 16: ...l environnement Pour des informations sur la garantie se reporter au manuel du moteur R GLES DE S CURIT Ceci est la s ret le symbole vif Il est utilis pour vous alerter aux dangers de blessure person...

Page 17: ...3 et ne doit pas tre utilis e pour des applications marines L omission d utiliser une g n ratrice appropri e et approuv e par U S Coast Guard pourrait entra ner des blessures corporelles ou des dommag...

Page 18: ...R D branchez toujours le c ble de bougie et placez le de fa on ce qu il ne soit pas en contact avec la bougie LORS DE TESTS D ALLUMAGE DU MOTEUR Utilisez un v rificateur de bougies d allumage approuv...

Page 19: ...un l ment de filtre du type sec et un pr filtre en mousse pour limiter le montant de salet et de poussi res entrant dans le moteur Interrupteur de starter Utilis lorsque vous faites un d marrage froi...

Page 20: ...e 8 1 Placez le fond du berceau de la g n ratrice sur une surface plate et unie Pour faciliter l assemblage placez temporairement l appareil sur des blocs 2 Faites glisser l essieu dans les deux suppo...

Page 21: ...85 N utilisez PAS de carburant qui contient du M thanol NE m langez PAS avec de l huile 2 Nettoyez la partie autour du bouchon du r servoir d essence enlevez le bouchon 3 Ajoutez lentement de l essenc...

Page 22: ...r s dans un difice qui pourrait tre occup Assurez vous que les gaz d chappement ne puissent entrer par une fen tre une porte une prise d a ration ou une autre ouverture qui pourrait leur permettre de...

Page 23: ...sence Voir la section Ne Pas Surcharger G n rateur D marrez le g n rateur et laissez le moteur se stabiliser avant de brancher les charges lectriques Branchez les charges lectriques en position ARR T...

Page 24: ...la prise 120 Volts c a 20 Amp res Prise de Courant Double Le prise de courant Figure 13 est prot g e contre la surcharge par un disjoncteur avec interrupteur bascule Utilisez chaque prise de courant p...

Page 25: ...rateur se stabiliser le moteur tourne r guli rement et les dispositifs branch s fonctionnent correctement 4 Branchez et mettez la charge suivante en marche 5 De nouveau laissez le g n rateur se stabil...

Page 26: ...es probl mes De plus si l eau entre par les fentes de refroidissement air une partie de l eau restera dans les creux et craquelures de l isolation du bobinage du rotor et du stator L eau et l accumula...

Page 27: ...it d alimentation ou sur les pi ces essentielles du carburateur versez un stabilisateur d essence dans le r servoir d essence et faites le plein avec de la nouvelle essence Faites marcher la g n ratri...

Page 28: ...harges sont branch es 1 Court circuit dans une charge branch e 2 Le g n rateur est surcharg 3 Court circuit dans le g n rateur 1 D brancher la charge en court circuit 2 Voir Ne Pas Surcharger G n rate...

Page 29: ...trophe naturelle ou toute autre force majeure hors du contr le du fabricant 198189F Rev B 12 31 2006 BRIGGS STRATTON POWER PRODUCTS GROUP LLC JEFFERSON WI USA deuxi me an s pare seulement GARANTIE DU...

Page 30: ...a de Protecci n Ambiental Para mayor informaci n acerca de la garant a consulte con el manual del propietario del motor REGLAS DE SEGURIDAD ste es el s mbolo de alerta de seguridad Sirve para advertir...

Page 31: ...n del combustible Mantenga la combustible alejada de chispas llamas abiertas pilotos calor y otras fuentes de ignici n NO encienda un cigarrillo o fume CUANDO PONGA EN FUNCIONAMIENTO EL EQUIPO Comprue...

Page 32: ...CUANDO AJUSTE O HAGA REPARACIONES A SU GENERADOR Siempre desconecte el alambre de la buj a y col quelo donde no pueda entrar en contacto con la buj a CUANDO PRUEBE LA BUJ A DEL MOTOR Utilice un compro...

Page 33: ...te Llene el motor con aceite aqu Tanque del Combustible El tanque tiene una capacidad de 7 galones americanos de gasolina sin contenido de plomo Tomacorriente Dobles de 120 Voltios AC 20 Amp Pueden se...

Page 34: ...plana Temporalmente coloque la unidad en bloques para ensamblarla f cilmente 2 Deslice el eje a trav s de ambos soportes de montaje en el marco de la camilla como se muestra en la Figura 15 3 Deslice...

Page 35: ...ire la tapa 3 Agregue lentamente combustible regular SIN PLOMO al tanque de combustible Use un embudo para evitar que se derrame Llene el tanque lentamente hasta aproximadamente 1 5 por debajo de la p...

Page 36: ...gases de escape no puedan entrar por ventanas puertas tomas de aire de ventilaci n u otras aberturas en un espacio cerrado en el que puedan acumularse Figura 17 Tenga en cuenta los vientos y las corri...

Page 37: ...ario del motor 4 Cierre la v lvula del combustible Vea No sobrecargue generador Encienda su generador y deje que el motor se estabilice antes de conectar las cargas el ctricas Conecte las cargas el ct...

Page 38: ...ecept culo Figura 20 est protegido en contra de sobrecargas por un disyuntor basculante Use cada recept culo para operar 120 Voltios AC de fase sencilla de cargas de 60Hz que requieren hasta 2 400 vat...

Page 39: ...el aparato conectado al mismo trabaja adecuadamente 4 Conecte y encienda la pr xima carga 5 De nuevo permita que el generador se estabilice 6 Repita los pasos 4 y 5 para cada carga adicional que usted...

Page 40: ...exterior NOTA NO recomendamos el uso de mangueras de jard n para limpiar el generador El agua podr a introducirse en el sistema de combustible del motor y causar problemas Adem s si el agua se introdu...

Page 41: ...vitar la formaci n de carbonilla en el circuito de combustible o en piezas esenciales del carburador a ada estabilizador de combustible al dep sito de combustible y llene este de gasolina nueva Haga f...

Page 42: ...se le contectan cargas 1 Corto circuito en una de las cargas conectadas 2 El generador est sobrecarga 3 Circuito del generador en corto 1 Desconecte la carga el ctrica en corto 2 Vea No Sobrerecarque...

Page 43: ...5500 Vatio el Generador Port til 43 NOTAS...

Page 44: ...tarios destinados al mantenimiento de las constantes vitales Esta garant a excluye los fallos debidos a hechos fortuitos y a otros acontecimientos de fuerza mayor que escapan al control del fabricante...

Reviews: