9

OPERATION

USING THE  GENERATOR

System Ground

The generator has a system ground that connects the
generator frame components to the ground terminals on
the AC output receptacles.The system ground is connected
to the AC neutral wire (the neutral is bonded to the
generator frame).

Special Requirements

There may be Federal or State Occupational Safety and
Health Administration (OSHA) regulations, local codes, or
ordinances that apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or
the local agency having jurisdiction.

• In some areas, generators are required to be registered

with local utility companies.

• If the generator is used at a construction site, there may

be additional regulations which must be observed.

Connecting to a Building’s Electrical

System

Connections for standby power to a building’s electrical
system must be made by a qualified electrician.The
connection must isolate the generator power from utility
power, and must comply with all applicable laws and
electrical codes.

Generator Location

Generator Clearance

Place generator in a well ventilated area, which will allow
for removal of deadly exhaust gas. DO NOT place
generator where exhaust gas could accumulate and enter
inside or be drawn into a potentially occupied building.
Ensure exhaust gas is kept away from any windows, doors,
ventilation intakes or other openings that can allow exhaust
gas to collect in a confined area (Figure 10). Prevailing
winds and air currents should be taken into consideration
when positioning generator.

• When using generator for backup power, notify utility

company. Use approved transfer equipment to isolate
generator from electric utility.

• Use a ground fault circuit interrupter (GFCI) in any damp or

highly conductive area, such as metal decking or steel work.

• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are worn,

frayed, bare or otherwise damaged.

• DO NOT operate generator in the rain or wet weather.
• DO NOT handle generator or electrical cords while standing

in water, while barefoot, or while hands or feet are wet.

• DO NOT allow unqualified persons or children to operate or

service generator.

Generator produces powerful voltage.
Failure to isolate generator from power utility
can result in death or injury to electric utility
workers due to backfeed of electrical energy.

WARNING

• Operate generator ONLY outdoors.
• Keep exhaust gas from entering a confined area through

windows, doors, ventilation intakes or other openings.

• DO NOT operate generator inside any building or enclosure

(even if doors or windows are open), including the generator
compartment of a recreational vehicle (RV).

Running generator gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide can cause nausea,
fainting or death.

WARNING

Figure 10 — Generator Clearance

Exhaust Port

Typical Generator Shown

• Keep at least 5 ft. (152 cm) clearance on all sides of generator

including overhead.

Exhaust heat/gases can ignite combustibles,
structures or damage fuel tank causing a fire.

WARNING

Summary of Contents for 30253

Page 1: ...el Generador 1 800 743 4115 M F 8 5 CT web www briggsandstratton com BRIGGS STRATTON POWER PRODUCTS GROUP LLC JEFFERSON WISCONSIN U S A Manual No 198171GS Revision 1 11 14 2005 Before using this produ...

Page 2: ...on refer to the engine operator s manual SAFETY RULES This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to a...

Page 3: ...less colorless poison gas Breathing carbon monoxide can cause nausea fainting or death WARNING WHEN ADDING OR DRAINING FUEL Turn generator OFF and let it cool at least 2 minutes before removing fuel c...

Page 4: ...ent sparks smokes or emits flames unit vibrates excessively Improper treatment of generator can damage it and shorten its life CAUTION WHEN ADJUSTING OR MAKING REPAIRS TOYOUR GENERATOR Disconnect the...

Page 5: ...peration of 120 and or 240 Volt AC 30 Amp single phase 60 Hz electrical lighting appliance tool and motor loads Air Cleaner Protects engine by filtering dust and debris out of intake air Choke Lever U...

Page 6: ...lign the handle so it will slide over the handle supports 2 Insert carriage bolts through holes from outside of the unit and attach a plastic knob from inside of unit Figure 2 Tighten by hand BEFORE S...

Page 7: ...fuel gauge to close it Figure 4 IMPORTANT The vent knob should be closed whenever you move the generator or transport the fuel tank WHEN ADDING FUEL Turn generator OFF and let it cool at least 2 minut...

Page 8: ...l tank MUST be filled with it lying flat not slanted or standing upright Figure 9 DO NOT let the fuel valve and quick connect come in contact with any dirt To place the fuel tank back on the unit foll...

Page 9: ...a confined area Figure 10 Prevailing winds and air currents should be taken into consideration when positioning generator When using generator for backup power notify utility company Use approved tra...

Page 10: ...oad Generator Start generator and let engine stabilize before connecting electrical loads Connect electrical loads in OFF position then turn ON for operation Turn electrical loads OFF and disconnect f...

Page 11: ...up to 2 775 watts of power at 23 1 Amps for 120 Volts 5 550 watts of power 5 55 kW at 23 1 Amps for 240 Volts The outlet is protected by a push to reset circuit breaker 120 Volt AC 20 Amp Duplex Recep...

Page 12: ...to stabilize engine runs smoothly and attached device operates properly 4 Plug in and turn on the next load 5 Again permit the generator to stabilize 6 Repeat steps 4 and 5 for each additional load N...

Page 13: ...lean generator Water can enter engine fuel system and cause problems In addition if water enters generator through cooling air slots some of the water will be retained in voids and cracks of the rotor...

Page 14: ...Figure 5 earlier To prevent gum from forming in fuel system or on essential carburetor parts empty entire contents of both supplied fuel stabilizer containers into fuel tank and fill with fresh fuel...

Page 15: ...it in a connected load 2 Generator is overloaded 3 Shorted generator circuit 1 Disconnect shorted electrical load 2 See Don t Overload Generator 3 Contact local service facility Engine will not start...

Page 16: ...16 NOTES NOTES...

Page 17: ...ectric powered pressure washers used for commercial purposes are not warranted NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN WARRANTY ON BRIGGS STRATTON PRODUCTS SAVE YOUR PROOF OF PURCHASE RECEIPT...

Page 18: ...t le California Air Resources Board Pour des informations sur la garantie se reporter au manuel d utilisation du moteur R GLES DE S CURIT Ceci est la s ret le symbole vif Il est utilis pour vous alert...

Page 19: ...e g n rateur et laissez le refroidir au moins 2 minutes avant de retirer le capuchon du r servoir de carburant Desserrez lentement le capuchon pour laisser la pression s chapper du r servoir Remplisse...

Page 20: ...ivement Un traitement inappropri du g n rateur risque de l endommager et de raccourcir sa dur e d utilisation ATTENTION LORSQUE VOUS R GLEZ OU R PAREZ VOTRE G N RATEUR D branchez toujours le c ble de...

Page 21: ...service Filtre air Utilise un l ment de filtre du type sec et un pr filtre en mousse pour limiter le montant de salet et de poussi res entrant dans le moteur Fixation de mise la masse Consultez l agen...

Page 22: ...n e d un c t l autre afin d aligner la poign e et de la faire glisser sur les supports 2 Ins rez le boulon dans le trou du c t droit de la poign e en regardant l arri re de l appareil et fixez le bout...

Page 23: ...s des aiguilles d une montre sur la jauge pour le fermer Figure 17 IMPORTANT Le bouton d a ration doit tre ferm chaque fois que vous d placez le g n rateur ou transportez le r servoir LORS DE L AJOUT...

Page 24: ...DOIT tre rempli lorsqu il est plat il ne doit pas tre inclin ou en position verticale Figure 22 NE LAISSEZ PAS la valve et le connecteur rapide en contact avec des salet s Pour replacer le r servoir...

Page 25: ...oment de choisir l endroit o vous installerez la g n ratrice Lorsque vous utilisez le g n rateur comme source d nergie de secours il est n cessaire d aviser les services publics d lectricit Utilisez u...

Page 26: ...s remettez en position MARCHE teignez les charges lectriques et d branchez les du g n rateur avant de l arr ter D passer la capacit de puissance ou d amp rage du g n rateur risque d endommager ce dern...

Page 27: ...cessitant jusqu 2 775 watts de puissance 2 775 kW 23 1 Amp res pour 120 Volts 5 550 watts de puissance 5 55 kW 23 1 Amp res pour 240 Volts La prise est prot g e par un disjoncteur de 30 Amp res du ty...

Page 28: ...tabiliser le moteur tourne r guli rement et les dispositifs branch s fonctionnent correctement 4 Branchez et mettez la charge suivante en marche 5 De nouveau laissez le g n rateur se stabiliser 6 R p...

Page 29: ...des probl mes De plus si l eau entre par les fentes de refroidissement air une partie de l eau restera dans les creux et craquelures de l isolation du bobinage du rotor et du stator L eau et l accumu...

Page 30: ...on de gomme dans le syst me d alimentation en carburant ou sur des pi ces essentielles du carburateur videz les trois r cipients de stabilisateur d essence fournis dans le r servoir et remplissez les...

Page 31: ...e en court circuit 2 Voir Ne Pas Surcharger G n rateur 3 Contacter n gociant de service Autoris Le moteur ne veut pas d marrer ou d marre et marche mal 1 La valve est en position Arr t 2 Le bouton d a...

Page 32: ...REMARQUES 32 REMARQUES...

Page 33: ...BRIQU PAR BRIGGS STRATTON IL N EST PAS N CESSAIRE DE L ENREGISTRER CONSERVEZ LE RE U COMME PREUVE D ACHAT SI LORS D UNE R CLAMATION DE GARANTIE VOUS NE POUVEZ PROUVER LA DATE INITIALE DE L ACHAT NOUS...

Page 34: ...i n Ambiental y el Consejo de recursos de aire de California Para mayor informaci n acerca de la garant a consulte con el Manual del Operario de Motor REGLAS DE SEGURIDAD ste es el s mbolo de alerta d...

Page 35: ...silenciador el tap n del dep sito de combustible y el filtro de aire est n instalados NO arranque el motor sin la buj a instalada Si se ha derramado combustible espere a que se evapore antes de arran...

Page 36: ...produce chispas humo o emite llamas La unidad vibra de una manera excesiva El tratamiento inadecuado del generador puede da arlo y acortar su vida productiva PRECAUCI N CUANDO AJUSTE O HAGA REPARACION...

Page 37: ...En para darle arranque al motor Col quelo en la posici n Off Apagado para detener un motor en funcionamiento Palanca del Cebador Usada cuando se est dando arranque a un motor fr o Pomo de Ventilaci n...

Page 38: ...a deslizarse sobre los soportes del mismo manubrio 2 Inserte el perno del soporte a trav s de los orificios desde interior de la unidad y sujete una perilla de pl stico desde el fuera de la misma unid...

Page 39: ...ustible Figura 30 IMPORTANTE Siempre que mueva el generador o traslade el dep sito de combustible el pomo de ventilaci n debe estar cerrado MONTAJE 39 Combustible Tanque Espacio de 1 5 Figura 29 Espac...

Page 40: ...orizontal no inclinado ni en posici n vertical Figura 35 Evite el contacto de la v lvula de combustible y del conector r pido con la suciedad Para volver a montar el dep sito de combustible en la unid...

Page 41: ...erador Cuando use un generador como poder de energ a auxiliar notifique a la compa a de utilidades Use el equipo de transferencia aprobado para aislar el generador de otra utilidad el ctrica Use un in...

Page 42: ...tricas Conecte las cargas el ctricas en la posici n de apagado OFF luego encienda ON para su operaci n Apague OFF las cargas el ctricas y descon ctelas del generador antes de parar el generador El sob...

Page 43: ...para 120Voltios 5 550Voltios de energ a 5 55 kW a 23 1 Amperios para 240Voltios La salida est protegida por un corto circuito de del tipo empuje para reposicionar 120 Volt AC 20 Amp Recept culos Dobl...

Page 44: ...onectado al mismo trabaja adecuadamente 4 Conecte y encienda la pr xima carga 5 De nuevo permita que el generador se estabilice 6 Repita los pasos 4 y 5 para cada carga adicional que usted tenga NUNCA...

Page 45: ...amos el uso de mangueras de jard n para limpiar el generador El agua podr a introducirse en el sistema de combustible del motor y causar problemas Adem s si el agua se introduce al generador a trav s...

Page 46: ...Off Figura 31 Para evitar la formaci n de carbonilla en el circuito de combustible o en piezas esenciales del carburador vac e totalmente los contenedores de estabilizador de combustible en el dep si...

Page 47: ...ecarga 3 Circuito del generador en corto 1 Desconecte la carga el ctrica en corto 2 Vea No Sobrerecarque Generador 3 Contacte el distribuidor de servicio autorizado El motor no se enciende o se encien...

Page 48: ...RVICIO DE BRIGGS STRATTON PRODUCTS GUARDE SU RECIBO DE COMPRA SI NO APORTA LA PRUEBA DE LA FECHA DE COMPRA INICIAL SE UTILIZAR LA FECHA DE FABRICACI N DEL PRODUCTO PARA DETERMINAR EL PER ODO DE GARANT...

Reviews: