Braeburn 229100 Owner'S Manual Download Page 1

TROUBLESHOOTING

SYMPTOM

DIAGNOSTIC STEPS

2. Check voltage at humidifier control terminals.  

    There should be no voltage for Power Humidifier.

    Voltage should be 20-30 VAC for most others.
3. Inspect humidifier wiring. Refer to wiring diagrams.

DO NOT LEAVE IN "ON" POSITION, OVER HUMIDIFICATION WILL OCCUR.

1. Set thermostat to operate both furnace burner and blower.

    Operation may be necessary for system power. 

No Humidifier

Operation in

"ON" position

1. Humidity level in the home is higher than knob setting.

    Humidifier control will not operate the humidifier until 

    humidity level is reduced.

Humidifier 

operation in

"ON" position

only

1. When the humidity in the home is less than the knob 

    setting, the control will operate humidifier until the

    humidity is higher. Reduce knob setting.
2. Use "ON" position. Verify that the humidifier operates. 

1. Check voltage at humidifier control terminals.  

    There should be no voltage for a Power Humidifier. 

    Voltage should be 20-30 VAC for most others.
2. If mounted on return air duct, make sure humidifier control

    is at least 24" upstream of humidifier's air discharge.

Humidifier 

turns on and 

off repeatedly

3. Remove wires from control terminals.  If humidifier 

    continues to operate, check solenoid valve.

Humidifier 

operation

continuous

WIRING

WARNING!

  

Disconnect electrical power before beginning installation. 

The wiring must conform to all building codes and ordinances as required by 

local and national code authorities having jurisdiction for this installation. 

Refer to the following wiring diagrams. 

CHECKOUT

With furnace in operation, turn humidistat to "ON" position. Observe 

humidifier operation.

SETTINGS

WARNING!

  

Do not set relative humidity too high during cold weather. Over 

humidification can result in condensation, structural damage and mold.  

Condensation within a building's structure can cause loss of structural 

strength. Condensation can also enable mold and mildew growth resulting in 

personal injury and damage to building structure and contents. 

Refer to OPERATION for proper settings. 

I. SAFETY

WARNING!  Improper electrical wiring can result in fire or loss of humidity 

control.  Disconnect electrical power before installing and servicing. Failure to 

disconnect electrical power may result in injury or death. The wiring must 

conform to all building codes and ordinances as required by local and 

national code authorities having jurisdiction for this installation.
The 229100 must be installed by a qualified Technician. Failure to properly 

install the 229100 may result in property damage or personal injury. 
Homeowners must read instructions and understand the operation of the 

229100 and the humidifier(s) it controls.
Improper operation can result in over or under humidification. Over 

humidification can result in condensation, structural damage and mold.  

Condensation within a building's structure can cause loss of structural 

strength.  Condensation can also enable mold and mildew growth resulting in 

personal injury and damage to building structure and contents.

OUTDOOR

TEMPERATURE

RECOMMENDED

SETTING

INSTALLER: PLEASE LEAVE OWNERS MANUAL WITH HOME OWNER.

HUMIDISTAT OWNERS MANUAL

II. APPLICATION 

The 229100 humidistat provides low voltage control of humidifiers installed in 

central heating systems.  The humidistat has a SPST switch and is designed 

for mounting on the return air duct.
RANGE: 10% to 85% RH   ELECTRICAL RATING: 30 VAC / 60 VA

OPERATION

Set the control knob to the desired humidity 

setting. The recommended setting for 

optimum humidification is 30% to 50%. The 

vertical position on the knob is approximately 

42% RH. 
Setting the humidistat above or below the 

recommended settings may not provide 

satisfactory results for your home.

229100

40

°

F     4

°

C

45

30

°

F    -1

°

C

40

20

°

F    -7

°

C

35

10

°

F  -12

°

C

 0

°

F  -18

°

C

30

25

-10

°

F - 23

°

C

-20

°

F  -29

°

C

20

15

III. INSTALLATION INSTRUCTIONS

PRECAUTIONS

The installer must be a qualified technician. Disconnect electrical power 

before beginning installation. Do not install the humidistat on the warm air 

duct. Conduct a thorough checkout before leaving the installation.

DUCT MOUNTING ON THE RETURN AIR - PREFERRED METHOD

Do not install the humidistat on the warm air duct or within 48” of  UV light.

1.

 Locate the humidistat at least 24" upstream of the humidifier or         

    bypass on the return air duct.  Avoid areas of direct radiation like  

 

    secondary heat exchangers in the fan compartment.

2.

 Remove face by inserting screwdriver into pry slot and twisting 

    (see fig 2) 

3.

 Use the plastic duct mount plate as a template. Accurately mark and  

    drill the (4) 3/32”mounting holes and cut away the 4-1/4” x 2-1/2”     

    section of the duct inside the duct mount plate.

4.

 Place duct mount base gasket on the humidistat base and   mount the  

    base with four screws.  Low voltage wire may enter the humidistat    

    under the gasket (see fig 2).

5.

 Connect wires to screw terminals on the control assembly as shown in  

    wiring diagrams. Replace face and knob.  

WALL MOUNTING INSTRUCTIONS

NOTE:

 

Requires wall mount kit (Model 229110)

1.

 Chose a location for the 229100 about five feet above the floor              

    on an inside wall with average room temperature and relative    

    humidity conditions.

2.

 Drill a small hole in the wall and run low voltage wiring to the    

    location chosen. Pull about 6” of wire through the hole. Use the entire          

    mounting gasket (both inside and outside portions) to seal the wall            

    opening or use foam tape to prevent drafts from affecting the    

 

    humidistat operation. (see fig. 3)

3.

 Remove the knob on the humidistat. Squeeze the top and    

    bottom of the base to release the face of the humidistat.

4.

 Mount the base horizontally over the wires. Attach directly to    

    the wall, using the two screws provided in the slotted holes.

5.

 Connect wires to screw terminals on the control assembly as    

    shown in wiring diagrams. Replace face and knob.   

Reviews: