The expansion zones may be wired to either the top or bottom communication terminals on the main panel 
or to the top or bottom communication terminals on the expansion panel. This wiring flexibility allows the 
installer to choose the most flexible, cost effective wiring for the installation.  

Each expansion panel must have a 5 Wire connection for proper communication. It is not necessary to use 
shielded wire for the panel to panel connection. 18 - 20 Gauge solid thermostat wire or similar is acceptable. 
When wiring the expansion panels be sure to connect the terminals from one panel to the next using the 
following terminal connections. 

5

 Main Panel       to 

Expansion Panel

      COM1          

       COM1 

 

      COM2          

       COM2

      GND       

  

       GND

     COM3          

       COM3

      COM4         

       COM4

    

Expansion Panel     to      Expansion Panel

         COM1       

   

 COM1   

         COM2       

   

 COM2

         GND       

   

 GND

         COM3       

   

 COM3

         COM4       

   

 COM4

MAIN Panel to Expander

Expander to Expander

 

            

Terminal    Qty.    Function      Description

  PANEL 

24V 

INPUT 

24 VAC Transformer Power 75 VA Maximum 

  POWER 

24C 

INPUT 

24 VAC Transformer Common 

  DAMPERS 

PO     

OUTPUT 

24 VAC Power Open Zone Damper Terminal 

   

C  

OUTPUT 

Zone Damper Common Terminal 

   

PC     

OUTPUT 

24 VAC Power Close Zone Damper Terminal

  EXPANSION 

COM1 

OUTPUT 

Expander Panel Communication

   

COM2 

OUTPUT 

Expander Panel Communication

   

GND 

INPUT 

Expander Panel Communication Ground

   

COM3 

INPUT 

Expander Panel Communication

   

COM4 

INPUT 

Expander Panel Communication

  THERMOSTAT 

R       

OUTPUT 

24 VAC Thermostat Power

   

Y1     

INPUT 

1st Stage Compressor Call

   

Y2     

INPUT 

2nd Stage Compressor Call

   

W1/E/AX1  

INPUT 

[W1] 1st Stage Conventional Heat Call [E] Emergency Heat Call

   

 

 

 

[AX1] 1st Stage Auxiliary Heat Call

   

W2/AX2     

INPUT 

[W2] 2nd Stage Conventional Heat Call [AX2] 2nd Stage Auxiliary Heat Call

   

O/B/W3     

INPUT 

[O] Cool Active Reversing Valve Call [B] Heat Active Reversing Valve Call

   

 

 

 

[W3] 3rd Stage Conventional Heat Call

   

G               

INPUT 

Fan Call

   

L               

OUTPUT 

System Malfunction Indicator

   

C               

OUTPUT 

24 VAC Transformer Common

   

RESET BUTTON 

 

Press once to restart panel

   

 

 

 

Hold for 5 seconds to reset panel and reset all factory defaults.

   

ZONE ADDRESS DIP SWITCHES 

See Zone Addressing (section 4)

   

WIRE STRIP GUIDE 

 

Wires should be stripped 3/8 inch minimum.

  

ZONE PANEL EXPANDER WIRING TERMINALS

1

2

3

4

5

6
7

Summary of Contents for 140424

Page 1: ...ing for the main panel and expansion panel before applying transformer power This panel is designed for professional installation and is to be installed and configured as described in this manual Any...

Page 2: ...tronic self resetting current limiting for panel power and damper zones Configuration Zone number by switch setting Maximum Zones 2 Zones Per Expander Panel Up to a Maximum of 14 Two Zone Expanders 32...

Page 3: ...all stud roof truss or the return air plenum For appearance mount the panel near the main panel for easy panel to panel wiring Remove the panel cover and use the base as a template to drill mounting h...

Page 4: ...l wiring instructions for all systems Specific wiring will vary depending on the type of thermostats and dampers used for the installation NOTE Up to 2 wires can be inserted into each terminal positio...

Page 5: ...MPERS PO 2 OUTPUT 24 VAC Power Open Zone Damper Terminal C 2 OUTPUT Zone Damper Common Terminal PC 2 OUTPUT 24 VAC Power Close Zone Damper Terminal EXPANSION COM1 2 OUTPUT Expander Panel Communication...

Page 6: ...Zones Located Remote to Main Panel Remote Panels Wired in Star Configuration 6 Main Panel Expander Panel Zones 5 6 Expander Panel Zones 7 8 Expander Panel As Needed Daisy Chain All Zones Located at Ma...

Page 7: ...Damper PO C PC PO COM PC Zone Panel 3 Wire Damper 7 Thermostat Wiring 3 2 1 HEAT 1 COOL R 24 VAC Power W1 Heat Call Y1 Cooling Call G Fan Call C 24 VAC Transformer Common Note 1 2 HEAT 2 COOL R 24 VAC...

Page 8: ...ll G Fan Call C 24 VAC Transformer Common Note 1 3 HEAT 2 COOL With Auxiliary Heat R 24 VAC Power O B Changeover Valve Note 2 L Optional System Fault Monitor AX1 Auxiliary Heat Relay 3rd Stage Heating...

Page 9: ...ON OFF OFF OFF 9 and 10 OFF ON OFF OFF 11 and 12 OFF OFF ON OFF 13 and 14 OFF OFF OFF ON 15 and 16 ON ON OFF OFF 17 and 18 ON OFF ON OFF 19 and 20 ON OFF OFF ON 21 and 22 OFF ON ON OFF 23 and 24 OFF...

Page 10: ...ar check wiring and ensure expansion zones have power 5 Press HOLD FOR EXIT for 3 seconds to complete adding zones Operation 6 The Zone Panel Expander has built in LED s to tell the installer and the...

Page 11: ...the communication terminals To locate the expander panel with the invalid address view the expander panel status LED The status LED will be flashing red Duplicate Address on Expansion Panel Displayed...

Page 12: ...opy of this warranty Visit us online www braeburnonline com warranty Phone us 866 268 5599 Write us Braeburn Systems LLC 2215 Cornell Avenue Montgomery IL 60538 5YEAR WARRANTY LIMITED Braeburn Systems...

Reviews: