Bradley Terreon Multi-Fount Series Installation Instructions Manual Download Page 13

Terreon® Quadra-Fount™ Wall-Hung Washfountain with Adaptive Infrared Control

Installation Instructions

MF2949/IR

13

Bradley Corporation • 215-1249 Rev. H; EN 03-045

9-15-2003

Solenoid Valve Troubleshooting

CAUTION: Turn off electrical and water supplies to unit before troubleshooting.

Problem: 

An individual operating station fails to shut off and drips.

Cause: 

There is debris trapped between the diaphragm and the valve seat.

Solution:

Remove debris between diaphragm and the valve seat.

1. Disconnect the wires to the appropriate solenoid valve by firmly pulling the fully insulated disconnects

(not the wires) from the coil located on top of the valve.

2. Loosen the screw on top of the coil and remove.
3. Using a small wrench, loosen the bonnet nut, unscrewing counterclockwise, and gently tip forward

to remove from the valve body. Be careful not to lose the armature or spring.

4. Remove the diaphragm. Remove any particles that have been trapped between the diaphragm

and the valve seat. Rinse off the diaphragm and inspect for damage. Make sure both orifices are
open.

5. Reassemble in reverse order. Do not overtighten the bonnet nut or you may crack the plastic

valve body. Hand tight plus 1/8 turn is sufficient.

6. Reconnect the wiring per Figure 9 on page 9.

Problem: 

An individual operating station fails to turn on.

Cause: 

A failed coil for the valve, or loose electrical connection to the terminal.

Solution:

Test the station to determine cause.

1. Disconnect the wires from the coil of an adjacent valve. Disconnect the wires from the problem

valve and reconnect to the adjacent valve.

2. Turn on electrical and water supplies to the unit. Pass your hand in front of the sensor of the

problem station, and the adjacent station should operate.  
If the adjacent station operates and cycles normally, replace the coil on the problem valve.
If the adjacent valve fails to turn on, inspect the wires from the sensor cable and preform the
following:

make sure there are no breaks and that the fully insulated disconnect terminals are firmly
crimped in place;

• turn off electrical and water supplies;
• reconnect to the adjacent valve and turn on electrical and water supplies to the unit;
• pass your hand in front of the sensor. If the station still fails to turn on, replace the sensor.

Summary of Contents for Terreon Multi-Fount Series

Page 1: ...f 13 9 15 2003 P O Box 309 Menomonee Falls WI 53052 0309 TEL 1 800 BRADLEY FAX 262 251 5817 http www bradleycorp com IMPORTANT Read through this installation manual to ensure proper installation Make...

Page 2: ...itutional purchaser and does not extend to any others including consumer customers of commercial institutional purchasers 6 This warranty is in lieu of all other warranties expressed or implied includ...

Page 3: ...d waste connection Pipe sealant and plumber s putty 110 VAC power source for 110 24 VAC plug in transformer supplied OPTIONAL Bradley recommends installing an electrical cut off switch to the unit Thi...

Page 4: ...l frame assembly IMPORTANT Make sure that the water is completely shut off before beginning installation 1 Rough in hot and cold supply lines through the wall 2 Rough in a drain waste connection throu...

Page 5: ...ps 1 4 nuts and washers provided 3 Connect the 1 2 NPT female end of the stop check valves to the rough ins 5 Insert the filter washers provided into the swivel nut at the end of the supply hoses 6 Co...

Page 6: ...assembly on the exposed portion of the screws Connect Flexible Hose at this end Solenoid Assembly Pedestal Frame 1 4 20 x 5 8 Screws Figure 3 Step 5 Install pedestal panels 1 Install three 1 4 20 x 1...

Page 7: ...ex head bolts 13 32 I D plain washers anchor plates lockwashers and hex nuts provided see Figure 5 4 Uncoil the infrared sensor leads and plastic tubing from the rear of the backsplash 5 Slide the bow...

Page 8: ...es into four solenoid tube connectors by loosening the tube connector cap and firmly pushing tubing into tube connector until the tubes are fully seated then re tighten connector cap see Figure 7 IMPO...

Page 9: ...the main water supply to the Quadra Fount and check for leaking 3 Pass your hand in front of each sensor until air is purged from the lines Step 9 Install top cover 1 Install the threaded rods into t...

Page 10: ...3 8 screw supplied through the welded nut on the bottom flange of the access panel see Figure 9 DO NOT tighten 2 Position the access panel by sliding the screw into the bracket slot on the pedestal f...

Page 11: ...Terreon Solid Surface material Bradley recommends additional care and maintenance for the darker colored Terreon for complete instructions on this additional maintenance see Bradley document 1505 IMP...

Page 12: ...e manufactures instructions Many of these products leave a protective coating the helps prevent future smears and fingerprints Grease and Oil To remove grease and oil use a quality commercial detergen...

Page 13: ...ke sure both orifices are open 5 Reassemble in reverse order Do not overtighten the bonnet nut or you may crack the plastic valve body Hand tight plus 1 8 turn is sufficient 6 Reconnect the wiring per...

Reviews: