S59-2005T1

Bradley TMVT1 Thermostatic 

Mixing Shower Valve

Table of Contents

Safety Information ............................................................2
Supplies Required ............................................................2
LCD Display Information ...................................................2
Rough-In ...........................................................................3
Connect Valve and Adjust Valve Temperature ..................4
Test Unit ............................................................................5
Attach Escutcheon and Handle ........................................5
Troubleshooting ................................................................6

Specifications

Inlet Connections:  

1/2" NPT 

Outlet Connections: 

1/2" NPT 

Temperature Range: 

Cold - 110°F 

Maximum Pressure: 

125 PSIG 

Inlet Temperature, Hot: 

120°–180°F 

Inlet Temperature, Cold: 

40°–80°F 

Minimum Temp. Differential  
(From valve set point): 

20°F

Read the instructions in this manual before 

beginning installation. Save these instructions 

and refer to them for inspection, maintenance, 

and troubleshooting information.

For questions regarding the operation, installation or maintenance of this 
product, visit bradleycorp.com or call 800.BRADLEY (800.272.3539).

Product warranties and parts information may also be found under 
“Resources” on our website at bradleycorp.com.

For use with shower heads rated 

at 5.7 L/min (1.5 gpm) or higher.

Summary of Contents for Equa-Flo TMVT1

Page 1: ...PT Outlet Connections 1 2 NPT Temperature Range Cold 110 F Maximum Pressure 125 PSIG Inlet Temperature Hot 120 180 F Inlet Temperature Cold 40 80 F Minimum Temp Differential From valve set point 20 F Read the instructions in this manual before beginning installation Save these instructions and refer to them for inspection maintenance and troubleshooting information For questions regarding the oper...

Page 2: ...njury including scalding chilling and or death depending upon system water pressure changes and or supply water temperature changes Hot limit screw is set in the maximum temperature position Failure to properly adjust may result in serious scalding This valve may not protect from scalding if there is a failure of other temperature controlling devices elsewhere in the plumbing system Excessive heat...

Page 3: ...Depth 3 1 8 79 Min Depth 1 2 NPT Plug not supplied Shower Only Installation 5 127 6 1 2 165 w Stops 2 1 2 64 w o Stops Hot Cold Front View See Step 2 for required valve adjustment and Back to Back installation Back to Back Installation Hot Cold Standard Install Supplies Reversed mm 8 203 72 1829 40 1016 Temperature Probe Tee on Bottom of Valve 1 2 NPT 1 2 NPT 1 2 NPT Plug not supplied 3 1 2 89 Min...

Page 4: ...The standard preset factory temperature setting is 110 F 43 C Consult proper medical and or safety authorities for the optimum temperature recommended for your particular application Back to Back Installation On the valve that is backwards Turn off hot and cold supplies Remove 2 screws that hold down cap Remove entire valve assembly from the valve body and rotate 180 Arrow on cap must point to HOT...

Page 5: ...r supply is turned off check to make sure the cold water is reduced to 5 GPM or less If the cold water is reduced properly reopen the hot water supply Shut the cold water supply off by closing the cold water inlet valve or supply check valve While the cold water supply is off check to make sure that the hot water flow has shut down If hot water is shut down reopen cold water supply Test unit weekl...

Page 6: ... and repair is complete Problem Cause Solution External leaks in the system Either the NPT joints or the O rings have been damaged Replace the NPT joints and or O rings where necessary For replacement of O rings order the O ring seat kit as specified in the included Service Guide Limited water flow Dirt and debris have collected on the stop check valve seat limiting the movement of the stop checks...