![Bradley E19-130 Installation Manual Download Page 3](http://html1.mh-extra.com/html/bradley/e19-130/e19-130_installation-manual_2799931003.webp)
3
Installation
E19-130
Bradley •
215-152E Rev. S; ECN 17-05-039
7/18/2017
Supplies Required:
• Teflon tape and pipe sealant
• Piping to 1" BSP water supply inlet
• Adequate supply pipe supports
• Minimum 4" (102 mm) drain to accommodate 30 gallons
(115 liters) per minute discharge for shower waste
• Sign-mounting hardware
Assemble components
1. Assemble the components as shown on page 4.
2. Apply pipe sealant to all male-threaded pipe joints.
3. Use a strap wrench around pipes when tightening to
prevent marring.
4. The bottom edge of the showerhead should be
2134mm (7'-0") from the floor.
Connect water supply
NOTICE! Do not rely on Bradley’s Drench Shower to support
supply piping.
1. Connect water supply piping to 1" BSP inlet on
unit (piping supplied by installer). Provide adequate
supports (supplied by installer) for supply pipe using
pipe hangers or other means.
2. Mount the safety sign to the wall using sign-mounting
hardware supplied by installer.
Ø
78.7mm
(
3.
1")
All dimensions assume standard thread engagement.
Variations in manufacturing allow for +/- 3mm (1/8")
per threaded joint. To find the tolerance of a dimension,
add the number of thread joints in between a
dimension and multiply it by 3mm (1/8").
610mm
(24")
229mm
(9")
2134mm
(7'-0")
to Floor
158mm
(6-1/4")
201mm
(8")