Metering Air Valve
The air valve timer is located next to the tube connector on the
air valve body. The timer is capped with a filter to prevent dirt
build-up on the timer. The air valve timing can be adjusted from
5–60 seconds.
A
Remove filter cap and use a screwdriver to tighten or
loosen the timer (see illustration at right). Turning the
timer clockwise increases the time; turning the timer
counterclockwise decreases the time.
B
Continue to adjust until the timer is set at desired
length.
C
Replace filter cap over the timer.
Water Tube
Connector
Air
Valve
Filter
Cap
Air Tube
Connector
A
Push in the orange manual release button while
pulling the tube out (see illustration at right) to
disconnect the tube at the connector. No tools are
needed.
B
To correct a leak, press tubing firmly into the
connector and make sure it is seated.
C
If leak persists, remove tubing from the fitting, and
trim the tubing end square with a razor-sharp knife.
If leak continues, replace the fitting or contact your
Bradley representative for assistance.